Ecodesign requirements
REGULATION (EU) N. 2016/2281 FOR HIGH TEMPERATURE PROCESS CHILLERS
Model
Refrigerant : R513A
Operating temperature
Annual electricity consumption
Seasonal energy performance ratio
Parameters at full load and ambient temperature 35°C (Point A)
Rated refrigeration capacity
Rated power input
Rated energy efficiency ratio
Parameters at full load and ambient temperature 25°C (Point B)
Declared refrigeration capacity
Declared power input
Declared energy efficiency ratio
Parameters at full load and ambient temperature 15°C (Point C)
Declared refrigeration capacity
Declared power input
Declared energy efficiency ratio
Parameters at full load and ambient temperature 5°C (Point D)
Declared refrigeration capacity
Declared power input
Declared energy efficiency ratio
Others items
Capacity control
Degradation co-efficient chillers
GWP of refrigerant
ICEP080E
(air condenser)
Symbol
Value
Unit
t
7°C
°C
Q
79000
kWh/a
SEPR
5,2
[-]
P
55,15
kW
A
D
20,35
kW
A
EER
2,71
[-]
DC,A
P
61,83
kW
B
D
16,53
kW
B
EER
3,74
[-]
DC,B
P
67,87
kW
C
D
13,41
kW
C
EER
5,06
[-]
DC,C
P
73,29
kW
D
D
11,00
kW
D
EER
6,66
[-]
DC,D
Staged
C
0,9
[-]
dc
GWP
573
kg CO
2eq
(100 y)
ICEP080E-ICEP120E
ICEP100E
(air condenser)
Symbol
Value
t
7°C
Q
108660
SEPR
5,1
P
73,61
A
D
26,30
A
EER
2,7993
DC,A
P
82,29
B
D
21,94
B
EER
3,75
DC,B
P
90,37
C
D
18,33
C
EER
4,93
DC,C
P
97,86
D
D
15,48
D
EER
6,32
DC,D
Staged
C
0,9
dc
/
GWP
573
ICEP120E
(air condenser)
Unit
Symbol
Value
°C
t
7°C
kWh/a
Q
133000
[-]
SEPR
5,02
kW
P
87,03
A
kW
D
30,01
A
[-]
EER
2,9
DC,A
kW
P
97,45
B
kW
D
25,18
B
[-]
EER
3,87
DC,B
kW
P
107,5
C
kW
D
21,63
C
[-]
EER
4,97
DC,C
kW
P
115,85
D
kW
D
18,77
D
[-]
EER
6,2
DC,D
Staged
[-]
C
0,9
dc
kg CO
/
GWP
573
2eq
(100 y)
Unit
°C
kWh/a
[-]
kW
kW
[-]
kW
kW
[-]
kW
kW
[-]
kW
kW
[-]
[-]
kg CO
/
2eq
(100 y)
12