5. PRODUCT INFORMATION

5.1 Type key
e.g.: CC-HVAC 4 x 3,0 FC WM
CC
Comfort Controller
HVAC
Heating, ventilation and air-conditioning sys-
tems
4 x
Number of pumps 1-6
3,0
Maximum motor power P
FC
With Frequency Converter
WM
Wall model
BM
Floor model

5.2 Technical data

Mains supply voltage [V]:
Nominal current I [A]:
Protection class:
Max. admissible ambient temperature:
Mains side fuse protection:
6. DESCRIPTION OF THE PRODUCT AND THE
ACCESSORIES
6.1 Description of the control system

6.1.1 Function description

The Comfort Control System that is controlled by means of a
programmable logic controller (SPS) is used to control individ-
ual and multiple pumps. The respective controlled variable of
an installation is controlled in a load-sensitive manner by
means of corresponding signal transmitters. The controller has
an effect on a frequency converter in the case of installations
which are equipped with a frequency converter (version 'FC')
which in turn affects the speed of a pump. A modification of
the speed changes the flow volume and thus the power out-
put of the pump system.
Only the base-load pump is controlled in speed-controlled
installations. Depending on the load demand, uncontrolled
peak-load pumps are switched on and off automatically,
whereby the respective base-load pump assumes responsibil-
ity for fine-tuning to the preset setpoint. The control systems are
Component (see Fig. 2)
Central unit (CPU)
with 16E/8A (digital)
Analogue module 2E/1A
Digital module 4E/4A
Digital module 8E/8A
COM interface
Power supply unit 24V
Temperature module 6E
for temperature control modes
[kW]
2
3~400 V, 50/60 Hz
See name plate
IP 54
40°C
in accordance with wiring diagram
designed differently, depending on the number of pumps and
the control requirements. It is to be noted that the temperature
controls n=f(Tx) can be applied only with single pump drives.
Feed or return temperature-sensitive peak-load operation is
technically not feasible.
6.1.2 Construction of the control device
The construction of the control device depends on the capac-
ity of the pumps to be connected (direct-starting: Fig. 1.1 or
star/delta start-up: Fig. 1.2). It consists of the following main
components:
•Main switch: On/Off switching of the switchgear (Item No. 1)
•Touchscreen: Display of the operating data (see Menus) and
the operating state by means of the changing colours of the
backlighting. Optional menu selection and entering of param-
eters with the touch-sensitive surface (Item No. 2).
•Programmable logic controller: Modularly constructed SPS
with power supply unit. The respective configuration (see
below) is system-dependent (Item No. 3)
No.
With FC
1-3 pumps
M
3
N
3
O
-
O
-
P
3
Q
3
R
optional
33
4-5 pumps
6 pumps
3
3
3
3
3
-
3
-
3
3
3
3
optional
optional
Without FC
1-6 pumps
3
3
-
-
-
3
optional