Descargar Imprimir esta página

Daikin FTXF09AXVJU Manual De Instalación página 11

Publicidad

Idiomas disponibles

Idiomas disponibles

5
IMPORTANT: * The figures shown in the table are for information purpose only. They should be checked and selected
to comply with the local/national codes of regulations. This is also subject to the type of installation and
conductors used.
** The appropriate voltage range should be checked with label data on the unit.
Conduit mounting
plate
Conduit
Lock nut
CAUTION
• Entire PCB replacement required if fuse failure occurs.
• All wires must be firmly connected.
• Make sure all the wire do not touch the refrigerant piping, compressor or any moving parts.
• Make sure no external pressure is applied to the terminal connectors and wires.
• Make sure all the covers are properly fixed to avoid any gap.
• Recommended to use round crimp-style terminal for connecting wires to the power supply terminal block.
Connect the wires by matching to the indication on terminal block. (Refer to the wiring diagram attached on the
unit).
• Use the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
• Over tightening can damage the terminal screws.
• Do not connect wires of different gauges to same terminal.
• Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.
Connect wires of the
same gauge to both sides.
WIRING
Recommend using AWG14, stranded and
insulated wire for connections between indoor
and outdoor units.
Local code always supersedes recommendation.
1
Indoor
2
unit
3
Back
Note: Take care to ensure that all wiring
between indoor unit and outdoor unit has a
consistent connection. Any splices can cause
communication errors.
Attach insulation sleeve
Round crimp-style terminal
Do not connect wires of the
same gauge to one side.
1-9
Firmly fix the wires with the
terminal screws.
Outdoor
unit
1 2 3
L1 L2 GR
Firmly fix the wires
with the terminal
screws.
Ground
Circuit Breaker Rating
Class 09/12
15A
Class 18/24
20A
Electric wire
Do not connect wires
of different gauges.
Safety devices
in accordance
Power
with local and
supply 60Hz
national codes,
208-230V
i.e. a circuit
breaker

Publicidad

loading