7. Fault and trouble shooting
7.1 Controller Running Fault and Trouble Shooting
Fault
Fault Type
Code
Low Water
LP
Pressure
High Water
HP
Pressure
LL
Low water level
The water tower
HH
is hydrated
abnormally
E022
AI1Sensor Fault
E001
IGBT Fault
www.proindecsa.com / proindecsa@proindecsa.com
Reason
1. Sensor malfunctions;
2. Motor
rotates
in
direction;
3. No water intake / insufficient
water intake;
4. There is air in the pump
1. Abnormal pressure sensor;
2. The parameter is set for too
low values
1. Water level of the pool is too
low;
2. Water level switch line is
abnormal;
3. Water level switch type is set
correctly
1. Water
tower
floating
failure
1. Sensors are not connected;
2. Sensor wiring error;
3. Sensor open;
4. Sensor damage;
5. The open circuit detection
value is set to be too large
1. Speed up too fast;
2. Damaged
power
electronic
components;
3. Interference
caused
misaction;
Page 19
39
Solution
Check
whether
sensor is normal;
reverse
Check whether the motor steering
is correct;
Check whether the parameter
b00.09 is set for too large value;
Check that the water pump does
not drain the internal air
Check
whether
sensor is normal;
Check whether the parameter
b00.08 is set for too small value
Check the water inlet system;
Check the wiring of the water
level switch and the terminal S1;
Check whether the b00.21 settings
match the water level switch type
ball
Check the floating ball
Check
the
between the sensor and the
controller;
Check whether the sensor is
normal;
Check if b00.13 is set up too large
Extend the acceleration time;
Check whether there is any strong
interference around it;
by
Ask supplier for support
the
pressure
the
pressure
connection