Descargar Imprimir esta página

Vortice VORT T Manual De Instrucciones página 10

Ocultar thumbs Ver también para VORT T:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

ENGLISH
By pressing the SET button again (the warning SET=3.0v appears on the screen), you can
also enter the wind speed value (m/s) at which the fan stops. Use INCR/DECR to select the
value. Press the SET button to exit.
Mode A – Dominant parameter Wind Speed
Settings concern setting up the wind speed in which fans go down to the minimum
speed or they stop. To do this push the SET button (the message «SET=3.0v» will
appear on the screen) and push INCR/DECR buttons to regulate the wind speed
(value settable from 0.0v to 50.0v).
Clicking again the SET button, it is possible to insert also the temperature in which the
machine stops. (only if the control box is equipped also with the thermometer). Press the
SET button to exit.
CONFIGURATION
The configuration concerns the data for the thermometer and
the anemometer, so their regulation does not depend on which
mode is used.
To do this push both INCR/DECR buttons for 5 sec, till when on
the display appears CONF. Now you are in the programmation
so just click SET to scroll all parameters.
The parameters for the user are:
P.r.o.b.
Cor.t: temperature probe 1 correction.
SCAL: Celsius or Fahrenheit degrees
Air
SP.Lo: % of minimum speed (generally 10%, so fans does not work under the 10% of
the maximum speed)
SP.Hi: % of maximum speed (it can be 100% or less and it indicates that at full speed,
fans go to the 100% of the maximum speed of the machine).
P.b: is the proportional band, the °C/°F range in which the fan goes from the minimum
speed to the maximum one; for the industrial sector generally is set up on 20°C.
NOTE: in mode A, the proportional band is already set up when the wind speed is chosen
(see SETTINGS); in fact setting for example 8 m/s, blades have the max RPM at 0 m/s
and min ones at 8 m/s.
AnEM: turn on/turn off wind block when the wind speed is the same or upper then the
value set up with the SET button; put 0 to turn AnEM off and 1 to turn it on. In the indu-
strial sector generally is 0.
D.Se.R.: wind block action hysteresis.
t.int.: 0-10V integration time.
ImP.: number of pulses per revolution.
Circ. = blade circumference
Unit = unit of measure 0=m/s 1=mph 2=km/h
Star: % minimum starting speed.
InVE. = 0-1 Inversion of the 0-10V regulation as compared to temperature.
Press SET button to quit.
10

Publicidad

loading

Este manual también es adecuado para:

21137