• Verify the load by checking the pressure; if it is below 0.5 bars or above 5.0 bars
with the unit running, restore the load and vacuum deair for at least 30 minutes and
introduce 250 g.
• Clean the condenser with pressurised air.
• Connect or replace the condenser fan.
• Check the pressure; if it is below 0.5 bars with the unit running, clean the circuit or
replace the obstructed components (possibly the continuous flow capillary pipe).