delay
relay contact
max. switching voltage/
current (DC): 30 V DC/5A
max. switching voltage/
current (AC): 250 V AC/8A
max. switching capacity: 150 W / 2000 VA
Note: Switch and potentiometer settings are for illustration purposes only.
CLS200 and CLS300 Relay Output Connection and Solid-state
Switch Connection
The relay is shown
K2
in a de-energized/
3 2 1
unpowered state.
NC
NO
COM
K2 contact ratings:
• max. switching voltage/current
(DC): 250 V AC/8 A
• max. switching voltage/current
(DC): 30 V DC/5 A
Diode Protection
customer-supplied
diode protection
Page EN-8
Pointek CLS200/300 (Standard) – QUICK START MANUAL
switch bank
sensor
sensor
status
output
status
K3
2 1
K3 contact ratings:
• max. voltage: 30 V DC, 30 V peak AC
• max. current: 82 mA
• non-polarized
relay coil
trip
point
power
on
power supply
12–250 V AC/DC
Solid-state switch to customer's control
or instrumentation device.
The switch is shown in de-energized state.
relay coil
customer-supplied
diode protection
removable
terminal
block (not
polarity
sensitive)
solid-state switch
30 V DC, 30 V peak AC
82 mA (max)
A5E32221251