Switch Bank
4 dip switches (S1, S2, S3, and S5)
control settings for the alarm output.
The fifth dip switch (S4) is used only
to test the delay settings.
When S3 is set to ON, it inverts the
relay function, and the functioning of
S1 and S2.
Failsafe/Alarm Setting
Alarm Mode S3 status
High
ON
Low
OFF
Delay Settings: S1 and S2
High alarm/
S3-ON
overfill protection
Low alarm/dry run
S3-OFF
protection
Setup mode/run mode: S5
S5-ON
Setup
mode
S5-OFF
Run mode
Test settings: S4 (inverts the signal).
S4-ON
Enable test
S4-OFF
Normal operation
1.
The manual assumes that the pump should be turned off in the event of a failure. If this is
not the case in your process, make the appropriate connections to suit your application.
Page EN-10
Pointek CLS200/300 (Standard) – QUICK START MANUAL
1 2 3 4 5
ROCKER DOWN
1
: S3
Probe status
covered
uncovered
Effect of S3 position on functioning of S1 and S2
S1-ON
disables delay of alarm de-activation (alarm OFF)
S2-ON
disables delay of alarm activation (alarm ON)
S1-ON
disables delay of alarm activation (alarm ON)
S2-ON
disables delay of alarm de-activation (alarm OFF)
Used only during trip-point setup.
Used during normal operation (run mode) after setup is complete.
Check output status and sensor status LEDs to verify delay interval set
by potentiometer P1.
delay: alarm activation
delay: alarm deactivation
failsafe/alarm
test delay settings
set-up mode/run mode
Dip switches shown in OFF
(open) position.
Alarm status
activated (ON)
activated (ON)
Relay status
de-energized
de-energized
A5E32221251