Safety Precautions
General Disclaimer
• The information in this quick installation guide is subject to change due to product updates
or other reasons. This guide cannot replace the product labels or the safety precautions in
the user manual unless otherwise specified. All descriptions here are for guidance only.
• Before installations, read through the quick installation guide. For additional information,
please see the user manual.
• All operations should be performed by trained and knowledgeable technicians who are
familiar with local standards and safety regulations.
• Check the deliverables for correct model, complete contents, and intact appearance. Contact
the manufacturer if any damage is found or any component is missing.
• Use insulating tools and wear personal protective equipment when operating the equipment
to ensure personal safety. Wear anti-static gloves, clothes, and wrist strip when touching
electronic components to protect the inverter from damage. The manufacturer shall not be
liable for any damage caused by static electricity.
• Strictly follow the installation, operation, and configuration instructions in this guide and user
manual. The manufacturer shall not be liable for equipment damage or personal injury if you
do not follow the instructions. For more warranty details, please visit
warranty.
Safety Disclaimer
Warning
PV String Safety:
1. Ensure the component frames and the bracket system are securely grounded.
2. Prepare and use the recommended terminals when connecting them with the DC cable of the
inverter. If the terminals used do not meet the specifications, the damage caused is beyond
the responsibility of the device manufacturer.
3. Ensure the DC cables are connected tightly, securely, and correctly. Inappropriate wiring may
cause poor contacts or high impedances, and damage the inverter.
4. Measure the DC cable using the multimeter to avoid reverse polarity connection. Also, the
voltage should be under the max DC input voltage. The manufacturer shall not be liable for
the damage caused by reverse connection and extremely high voltage.
5. The PV strings cannot be grounded. Ensure the minimum insulation resistance of the
PV string to the ground meets the minimum insulation resistance requirements before
connecting the PV string to the inverter. R=Max. Input Voltage (V)/30mA.
6. The PV modules used with the inverter must have an IEC61730 class A rating.
Inverter Safety:
1. The voltage and frequency at the connecting point should meet the on-grid requirements.
2. Additional protective devices like circuit breakers or fuses are recommended on the AC side.
Specification of the protective device should be at least 1.25 times the maximum AC output
current.
3. PE cable of the inverter must be connected firmly.
4. Copper core cables are recommended for AC output cables. If you use aluminum wires,
please use copper-aluminum terminals for wiring.
5. If there is no battery in the PV system, the BACK-UP function is not recommended to
01