PROGRAMMING THE ZONE ADJUSTMENT PARAMETERS
• From this menu, designated by the symbol
possible to confi gure the adjustment parameters for the
currently displayed zone:
° summer/winter operating mode (default: winter);
° adjustment type (ON/OFF or proportional)
(default: ON/OFF);
° adjustment differential for the ON/OFF adjustment
(the value can vary between 0.1º and 1.0º, the
default is 0.3ºC).
• These menus can be accessed with the
• Press [OK] to enable the parameter (fl ashing fi eld) modifi cation and use the
arrows to modify it. Press [OK] again to fi nalise the modifi cation.
ESC
ESC
• The adjustment differential confi guration menu will only be displayed if the
confi guration adjustment type if ON/OFF.
• If the measurement is less than the minimum threshold in ON/OFF operation, then the
load is always inserted.
• In proportional operation, the adjustment has a temporary base of ten minutes, with
the following characteristics:
Tmis Tset + 0.6 °C [1.1 °F]
Tmis = Tset + 0.5 °C [0.9 °F]
Tmis = Tset + 0.4 °C [0.7 °F]
Tmis = Tset + 0.3 °C [0.5 °F]
Tmis = Tset + 0.2 °C [0.4 °F]
Tmis = Tset+ 0.1 °C [0.2 °F]
Tmis = Tset
6 minutes ON; 4 minutes OFF
Tmis = Tset - 0.1 °C [0.2 °F]
Tmis = Tset - 0.2 °C [0.4 °F]
Tmis = Tset - 0.3 °C [0.5 °F]
Tmis Tset - 0.4 °C [0.7 °F]
, it is
and
arrows.
ESC
ESC
relay OFF
1 minutes ON; 9 minutes OFF
2 minutes ON; 8 minutes OFF
3 minutes ON; 7 minutes OFF
4 minutes ON; 6 minutes OFF
5 minutes ON; 5 minutes OFF
7 minutes ON; 3 minutes OFF
8 minutes ON; 2 minutes OFF
9 minutes ON; 1 minute OFF
relay ON
- 57 -
Athena
Instruction Manual
and
ESC
ESC