101 SYSTEM SETPOINTS
Pump Start
Pressure
[ 60.0]psi
0-999.9
102 SYSTEM SETPOINTS
Pump Stop
Pressure
[ 90.0]psi
0-999.9
103 SYSTEM SETPOINTS
Pump Start
Delay Time
[
1] seconds
0-999
104 SYSTEM SETPOINTS
Pump Automatic
Stop Enabled
[ No]
105 SYSTEM SETPOINTS
Pump Minimum
Run Time
[10]minutes
10-30
106 SYSTEM SETPOINTS
Ramp Stop Option
MP700
[Yes]
107 SYSTEM SETPOINTS
Ramp Stop Option
Time
[10]sec
1-99
108 SYSTEM SETPOINTS
Solenoid Drain
Valve Option
[ No]
109 SYSTEM SETPOINTS
Automatic Weekly
Test Run
[ No]
110 SYSTEM SETPOINTS
Auto Weekly Test
Day Of The Week
[Tue]
111 SYSTEM SETPOINTS
Auto Weekly Pump
Test Start Time
[10:00:00]
112 SYSTEM SETPOINTS
Auto Weekly Test
Length Of Run Time
[10] minutes
10-30
113 SYSTEM SETPOINTS
Stop Motor during
Test on Alarm
[No]
114 SYSTEM SETPOINTS
Supervisory Power
Option
[No]
Mapa de las pantallas del OID (continuación)
1
1) SYSTEM SETPOINTS
2) USER PREFERENCES
3) TECH SCREENS
2
1) ANALOG SIGNALS
2) AUXILLIARY ALARMS
201 USER PREFERENCES
301
Set System Real
Controller Model
Time Clock
Number
[17:03:52]
[ MP300]
202 USER PREFERENCES
302
Set System Date
Transfer Switch
Supplied
[02/16/03]
[ No]
203 USER PREFERENCES
303
Set System Day
Nominal System
Of The Week
Voltage
[Sun]
[480]VAC
204 USER PREFERENCES
304
Log System Pressure
CPT Primary Voltage
Drop Events
Rating
[ No]
[ 480]
205 USER PREFERENCES
305
Low Pressure Event
Current Transformer
Trip Pressure
Ratio
[ 60]psi
0-999.9
[1200] /5
206 USER PREFERENCES
306
System Pressure Drop
Restart Time
Event Time Span
Delay
[ 5] seconds
0-20
[ 3]sec
207 USER PREFERENCES
307
Motor Full Load
Time Between
Amps
Pressure Log Samples
[ 65]Amps
[ 15] seconds 15-999
208 USER PREFERENCES
308
Auto Print Each
Low Voltage
Pressure Log Sample
Trip Percent
[No ]
[85]%
209 USER PREFERENCES
309
Low Voltage
Auto Print Each
Event Log Entry
Time Delay
[No ]
[ 5]sec
210 USER PREFERENCES
310
Selective Range
High Voltage Alarm
Printing
% of Nominal
[ 1] Before
1-99
[125]%
211 USER PREFERENCES
311
Selective Range
High Voltage
Printing
Time Delay
[ 1] After
1-99
[ 5]sec
212 USER PREFERENCES
312
High Discharge Press
Phase Loss % of
Alarm Option
Nominal Voltage
[ No]
[70]%
213 USER PREFERENCES
313
High Discharge
Phase Loss
Alarm Pressure
Time Delay
[175]
1-999
[5]sec
214 USER PREFERENCES
314
High Discharge Alarm
Start Transition
Time Delay
Time Delay
[ 8]sec
0-99
[ 2]sec
Page 12 of 32
Nombre del Archivo: Doc#605K Spanish.doc
CONFIG
CONFIG
TECH SCREENS
400 ANALOG SIGNALS
Analog Input 01
Slope:
[0.3401360]
TECH SCREENS
401 ANALOG SIGNALS
Analog Input 01
Offset:
[- 76.1904]
TECH SCREENS
402 ANALOG SIGNALS
Analog Input 1
Minimum Counts
120-7200
[ 200]
TECH SCREENS
403 ANALOG SIGNALS
Analog Input 01
Maximum Counts
120-7200
[2500]
TECH SCREENS
404 ANALOG SIGNALS
Analog Input 1
Minimum PSI
[ 3]
1-9999
TECH SCREENS
405 ANALOG SIGNALS
Analog Input 02
Slope
0-99
[ 0.0094996]
TECH SCREENS
406 ANALOG SIGNALS
Analog Input 02
Offset
0-999
[-75.2568]
TECH SCREENS
407 ANALOG SIGNALS
Analog Input 02
Minimum Counts
50-99
[
0]
TECH SCREENS
408 ANALOG SIGNALS
Analog Input 03
Slope
0-99
[0.0094996]
TECH SCREENS
409 ANALOG SIGNALS
Analog Input 03
Offset
0-999
[-75.2568]
TECH SCREENS
410 ANALOG SIGNALS
Analog Input 03
Minimum Counts
0-99
[ 0]
TECH SCREENS
411 ANALOG SIGNALS
Minimum Volts
0-99
[10]
TECH SCREENS
412 ANALOG SIGNALS
Phase AB Voltage
Slope:
0-99
[0.729750]
TECH SCREENS
413 ANALOG SIGNALS
Phase AB Voltage
Offset:
0-10
[6.52430]
501 AUX USER PROGRAM
AUX# 1
Enabled
[Yes]
502 AUX USER PROGRAM
AUX# 1
Input Number
[30]
503 AUX USER PROGRAM
651
AUX# 1
Input Contact Type
[NO ]
504 AUX USER PROGRAM
651
AUX# 1
Trip Time
[
0]sec
505 AUX USER PROGRAM
651
AUX# 1
Reset Time
0-10
[
0]sec
506 AUX USER PROGRAM
AUX# 1
Auto Reset Enabled
[Yes]
507 AUX USER PROGRAM
AUX# 1
Horn Enabled
[No ]
508 AUX USER PROGRAM
651
AUX# 1
Horn Silence
[No ]
509 AUX USER PROGRAM
AUX# 1
Disply on LCD
[No]
510 AUX USER PROGRAM
AUX# 1
Output1 Number
[ 0]
511 AUX USER PROGRAM
AUX# 1
Output2 Number
[ 0]
512 AUX USER PROGRAM
AUX# 1
Output3 Number
0-9999
[ 0]
513 AUX USER PROGRAM
AUX# 1
Record In Event Log
[No ]
514 AUX USER PROGRAM
AUX# 1
Text Message Number
[ 0]
0-40
0-999
0-999
0-19
0-19
0-19
0-27