MANUAL DE USUARIO - OPTIMA-31 10K / 20K / 30K
16: Output voltage calibration
Interface
17: Phase auto adapt enable / disable
Interface
OPTIMA 30K
Como el modelo 30K no ofrece la salida programable 2, las funciones 10 y 11 no están disponibles. Todas las demás funciones son iguales a
las de los modelos 10K y 20K.
10: Reserved
Interface
11: Reserved
Interface
www.xmart-ups.com
Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the output A voltage, and you
can calibrate it by pressing Up or Down according to the measurement from an external
voltage meter. The calibration result will be effective by pressing Enter. The calibration
range is limited within +/-9V. This function is normally used for parallel operation.
Setting
Parameter 2: it always shows PH.A as PHASE AUTO ADAPT.
Parameter 3: it allows enable or disable this function:
DIS: Disables this function. If disable UPS only accepts 120º difference between input
lines.
ENA: Enables this function. If enable, UPS will accept input lines with same phase or a
difference of 240ºC between them.
Setting
Reserve for future options.
Setting
Reserve for future options.
V. 170502-OPT-31 10K/20K/30K (SPANISH) -
41