Technical Data - Cooper Crouse-Hinds EVI Serie Instrucciones De Uso

Luminarias de suspensión sin equipo auxiliar para atmósferas explosivas.
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1. Safety Instructions
For skilled electricians and instructed
personnel in accordance with national
regulation, including the relevant standard and,
where applicable, in acc.with IEC 60079-17 on
electrical apparatus for explosive atmospheres.
❒ The luminaires must not be operated in Zone 0
and Zone 20.
❒ The tecnical data indicated on the luminaires
are to be observed.
❒ Changes of the design and modifications to the
luminaires are not permitted.
❒ The luminaires shall be operated as intended
and only in undamaged and perfect conditions.
❒ Only genuine CEAG spare parts may be used
for replacement.
❒ Repairs that affect the explosion protection, may
only be carried out by CEAG or a qualified
"electrician" and will subsequenctly have to be
cheked by an "expert".
❒ Do not keep these operating instructions inside
the luminaire during opertion.
❒ The national safety rules and regulations for
prevention of accidents and the following safety
instructions which are marked with an (
theses operting instructions, will have to be
observed.
2. Conformity with standards
This explosion protected luminaires meets the
requeriments of IEC/EN 60079-1, IEC/EN 60079-7,
IEC/EN 61241-1 and EN60598. It also complies with
the EC Directives for "Apparatus and protective
systems for use in explosive atmospheres" (94/9/EC)
and "Electromagnetic compatibility" (89/336/EEC).
It has been designed, manufactured and tested in
accordance to the state of the art and according to
EN29001 (ISO9001).
The luminaire are suitables for use in hazordous
areas, Zone 1 and 2 acc. to IEC60079-10-1 and Zone
21 and 22 acc. to IEC 60079-10-2.

3. Technical data

Application
II2 GD
Class I:
Exd /de IIC T
Class II:
Ex tD A21 IP67 T
Certificates:
LOM 02 ATEX2012X
IECEx-BKI 07.0031X
Others, contact us
Serie of types:
See Table 1
3)
Lamps to be use
:
See Table 1
Approval of the production
Quality assurance:
LOM 02 ATEX 9040
Degree of protection
acc. EN60598:
IP 67
Insulation class
acc. EN60598:
I
Temperature of use:
-50
o
C to + 55
≤ 250V
Rated voltage
Material of enclosure:
Metal aloy aluminium
without Cu,painted
polyester grey.
Material of glass Borosilicate
Storage temperature in original
Packing
-40
o
C a + 60
Terminals capacity:
See wiring diagram
Notes:
1) Special conditions for safe use of luminaires with direct entry.
The cable of the main connection will be adecuated for a temperature in continuos service,follow indicated.:
Lamps < 300W: for Tamb –20
o
C / + 40
Lamps > 300W < 500W:
for Tamb –20
o
C / + 40
o
C, Tw cable > 125
2) See table 2, thermal class acc. the lamp used.
3) Non included.
Entries of cables
Direct entry:
Indirect entry:
Dimensions:
4. Installation
¡The respective national regulations as
well as the general rules of engineering
which apply to the installation and operation of
explosion protected apparatus will have to be
observed!
¡Transport and storage of the luminaire is
permitted in original packaging only!
¡Pay attention when mounting or repairing the
luminaire, dont damage the fire-finish of the glass
adquired during moulding (abrasions, sanding,
etc.) that can weaking their mechanical functions!
Opening and closing the luminaires
¡The opening of luminaire always shall be
without voltage!
¡The luminaire is well closed when the
glass-collar and covers are completly
threaded on the luminaire enclosure!
See figures 4 and 5.
Dimensions for mounting:
Accesories for mounting:
Cable entries
) in
¡Mounting the selected cable entries
(cableglands or seals acc. needs) acc. type
and dimensions of the main conection cable,
following their manufacturer instructions!
¡The cable entries devices has to be the same
protection mode than the enclosure where they
are mounting!
¡Unused cabe entries have to be closed by a
correspondante certified blanking plug.
If the original blanking plugs are used , these
must be tightened with 15 Nm torque!
Main conection:
Lamps mounting
¡Only must be mounting apropiated lamps
for the supplied luminaire. See indications
in the general label of the luminaire!
¡Referred to the discharge lamps with
incorporate ignitor, only use these manufactured
2)
in acc. with the EC Directive of Electromagnetic
2)
compatibilty!
1)
1)
5.
Taking into operation
¡Prior to operation check the luminaire for
its proper funtioning and installation in
compliance with these operting instructions and
others applicable regulations!
Only carry out insulation measurements between PE
and external conductor L1 (L1, L2, L3) as well as
between PE and N.
o
C
-
measurement voltage: max. 1kV AC/DC
-
min. insulation: 2 MΩ
Then the luminaire have to be tightly closed.
o
C
o
C, Tw cable > 97
o
C ; para Tamb –20
o
C ; para Tamb –20
o
C / + 55
o
C, Tw cable > 140
2 x ¾" ISO 7/1, one plugged
2 x M25 x 1,5 ISO965-1,
one plugged
See figure 3.
See figure 3
See CEAG catalogue
See wiring diagram.
o
C / + 55
o
C, Tw cable > 112
o
C
o
C
6.
Maintenance
¡Observe the national rules applicable to
maintenance, servicing, inspection and
repairing of apparatus for explosive atmospheres,
as well as the general rules of engineering!
Servicing
¡The responsable of the safe use of these
apparatus is the property!
When servicing, in particular those components that
affect the explosion protection , will have to cheked,
e.g.:
❒ Housing and glass for any cracks or damage.
❒ The flameproof joint have to be clean,
undameged, without corrosion and perfect
greassed.
❒ Gaskets for their perfect conditions.
❒ Cable entries whitout corrosion.
❒ Terminlas and blanking plugs for their firm fix.
❒ Lamp replacement in acc. with the manufacturer
instructions.
❒ Type of lamps used in acc. with the luminaire
specifications.
¡The flameproof of these apparatus have to
be greassed permanentlly in order to ensure
it protection in front of the corrosion, water
ingrees and seize-up problems. Cleaning rest of
greasse and corrosion no using sharp metallic
devices who can damage the surface of the joint,
and greasing they using apropiate greasse
thermically and chemically stable, like e.g.:
    
Molikote
BR2 plus.
¡When the housing need to be repeinted, pay
attention that the flameproof joints rest without
Traks of coating!
Inspection
¡The nationals regulations have to be
observed!
E.g. in Spain the inspections of the installations in
hazardous areas, have to be done by "qualified"
personnel in accordance with the Electrotechnical
Low Votage Regulation following the indications
stablished in IEC 60079-17.
¡When the inspections are in degree of
"Detailled" or "Closed", the luminaires have
to be disconnected from the main conection!
Repairing
¡The nationals regulations have to be
observed. The tasks of
repairing have to be made by "qualified" personnel!
¡The reparation of the sealed part between the
collarand the glass have to be done by CEAG. The
users are not authorized to repair this sealed part!
¡All reparations have to be done without
voltage!
For repair electrical equipments in protection mode is
suggested follow the instructions indicated
in IEC 79-19.
¡Only use genuine CEAG spare parts!
Subject to alteration or supplement of this product
without any advertisement before.
Cooper Crouse-Hinds, S.A.
6