1.
Safety Instructions
This product should be Installed and
connected by skilled electricians and
instructed personnel in accordance with
60079-14 and the respective national
legislation on electrical equipment for
explosive atmospheres.
The national safety rules and regulations for
the prevention of accidents, as well as the
safety instructions, like this text set in bold-
italics in these operating instructions ma-
nual, shall be observed!
The luminaries must not be operated in Zone
0 or 20 hazardous areas.
The requirements of 60079-14 regarding
excessive dust deposits and temperature
must be considered by the user. The
indicated surface temperatures are not
related to a layer above 5mm thickness
Before opening, electrical power to the
luminaire must be turn off during at least
10minutes!
The temperature class and explosion group
stated on the luminaire shall be observed.
To ensure adherence to the temperature
class or surface temperature stated on the
type label of the luminaire, the permissible
ambient temperature shall be observed.
Light fitting shall be used for their intended
purpose and shall be undamaged and in a
perfect and clean conditions.
Keep tightly closed when in operation.
The technical data indicated in point 3 as
well as those indicated in light fitting, must
be observed.
Modifications or design changes to this
luminaries that can affect the explosion
protection are not permitted.
Avoid multiple, short time switching
operation
Only original COOPER Crouse-Hinds spare
parts may be used as replacements and for
repairs.
Repairs that affect the explosion protection
may only be carried out by
COOPER Crouse-Hinds or by a qualified
electrician in compliance with the respecti-
ve national regulations.
Prior to being put into operation, the
luminaries shall be checked in accordance
with the instructions as per section 6.
Before initial operation, any foreign matter
shall be removed from light fitting, do not
keep this operating instructions manual
inside of the luminaire during its operation.
2.
Conformity with standards
This light fitting is conform to the standards specified in the EC-Declaration of conformity. It has
been designed, manufactured and tested according to the state of the art and to DIN EN
ISO 9001, 94/9 EC: Equipment and protective systems intended for use in potentially explosive
atmospheres. The light fitting fulfill further requirements, such as the EC directive on electromagnetic
compatibility (2004/108/EC).
3.
Technical data
Apparatus marking acc. to 94/9/EG and directive:
EC-type examination certificate:
Rated voltage:
Rated current:
Power consumption
Luminous flux Φ
/Φ
at the end of rated
E
N
operating time
Terminals:
Degree of protection EN/IEC 60529:
Insulation class EN/IEC 60598:
Perm. ambient temperature:
The Ta range for electronic ballast is reduced up to +40ºC
due to their Tw, at higher temperature COOPER Crouse-Hinds cannot guarantee their normal life.
Storage temperature in original packaging:
Enclosure material:
Glass material:
Enclosure surface finish:
Color of enclosure (standard version):
Dimensions:
Cable entries:
4.
Field of application
This light fitting is intended for use in potentially explosive atmospheres in zones 1, 2 and 21, 22
in accordance with EN/IEC 60079-10. The enclosure materials used, including any external metal
parts, are high quality materials that ensure a corrosion resistance and resistance to chemical
substances according to the requirements for use in a "normal industrial atmosphere":
- Copper free aluminium alloy casting
- Plastic powder coating finish
- Stainless steel
- Borosilicate glass
In case of use in an extremely aggressive atmosphere, please consult to the manufacturer.
5.
Use/Properties
This light fitting can be use inside or outside to illuminate areas with potentially explosive
atmospheres, may be used only in places with low mechanical impact risk, due to the normal
operation in the industrial process. The temperature class, explosion group and permissible ambient
temperature can be found in the tables and technical data.
Light fittings suitable for their use as emergency or escape sign luminaire connected together with
a central or group battery system type CeaGuard 48 or similar with Cewa Guard technology for an
automatic function monitoring up to 20 luminaries per circuit (see Fig.1). The luminaries can be
use as escape sign light fitting in combination with self adhesive pictograms, Optional pictograms
can be selected from table 2 supplied as optional.
The data according to sections 2 and 4 shall be taken into account during use. Applications other
than those described are not permissible without a written declaration of consent from
COOPER Crouse-Hinds.
During operation the instructions stated in section 7 of the operating instructions shall be observed.
The sole responsibility with respect to the suitability and proper use of these luminaries lies with
the operator.
II 2 G Ex d IIC T5/T6 Gb
II 2 D Ex tb IIIC T58 T73°C Db
See table 1
LOM 02ATEX2013X
220-240V, 50/60Hz
176-275 VDC
30mA
16VA
75%
2x2,5mm
2
L y N, 6mm
2
PE ext.
IP 67
I
-20ºC to + 40ºC
-40ºC to + 60ºC
Aluminium alloy casting (Cu free)
Borosilicate glass
Plastic powder coating
RAL 7032, cover RAL 7016
See Fig. 2
2x3/4"NPT or 2xM25x1,5 or 2xM20x1,5,
one with blanking plug
Cooper Crouse-Hinds, S.A.