Communication
Problem
Cause
The communication module settings
are incorrect
The communication module
Communication
connections are incorrect
not possible
with analyzer
Communication settings (PLC or
third party software) are incorrect
Settings
Problem
Cause
The password entered is incorrect
It is impossible
to change the
The rotary selector at rear of main
settings (via
unit is in position 7
keypad)
The rotary selector at rear of main
unit is in position 7
It is impossible
to change the
The user is in the settings menu
settings (via
UCS software)
Possible solution
Check the parameters in the
settings menu, see "Settings
menu" on page 24
Check the connections,
see "Accessory module
connection diagrams" on
page 19
Check communication with
the UCS software
Possible solution
Enter the correct password
Set the selector to position 1
Set the selector to position 1
Exit the settings menu
pressing
for 1.5 s
8021572 | WM20 | © 2016 | CARLO GAVAZZI Controls SpA