4.6 Calibrate potentiometer
1 This function is used when calibrating the zero positions
on the knobs for depth feeding and travel feeding.
To calibrate the zero positions:
1 Scroll using the arrow keys and press OK when Calibrate
potentiometers" is shown.
The display shows: CALIBRATE 0 0. The left-hand digit
refers to the depth feeding and the right digit refers to the
travel feeding.
When the knobs are turned from the zero position the zeros
are shown and a number of >>>. The number of arrows
depends on how far the knobs are from the zero positions.
1 Remove the knobs by unscrewing the screws located on
the side of each knob. Use an allen key.
2 Turn the shafts until only two zeros are shown on the
display.
3 Fit the knobs again.
4 Adjust the plastic washer.
5 Confirm with OK".
6 Press the down arrow to continue to Back to the menu".

5. Hydraulic unit settings

This sub-menu contains information about the hydraulic unit
and functions for setting of units and the PIN code. The sub-
menu consists of six part menus:
5.1 Husqvarna PP 455E version
5.2 AM (American) units
5.3 Radio ID
5.4 ID Hydraulic unit
5.5. PIN code
5.6. Change the PIN code
5.1 Husqvarna PP 455E version
The display shows the version number, for example 2.0, for
the software.
Press the down arrow to continue to the next part menu.
5.2 AM (American) units
AM units. The display shows: AM units and ON or OFF. When
the function is ON American units are used in the menu
system.
Press the down arrow to continue to the next part menu.
SETTINGS AND ADJUSTMENTS
5.3 Radio ID
In order to make radio contact with the remote control and the
hydraulic unit, an ID number must be stated. The CAN cable
must be connected between the remote control and the
hydraulic unit to change the ID number.
Press OK when the display shows RADIOID 0 0.
The left-hand digit refers to the high byte and the right digit
refers to the low byte.
State, with the arrow keys, the high byte and press OK.
State, with the arrow keys, the low byte and press OK.
Press the down arrow to continue to the next part menu.
5.4 ID Hydraulic unit
From the factory the ID number is the same as the machine
number. If the remote control or the hydraulic unit are
replaced or reprogrammed, an ID number must be stated. As
a suggestion, change to the hydraulic unit's ID number.
The display shows the identity number for the hydraulic unit.
The identity number must be greater than 0.
Press the down arrow to continue to the next part menu.
5.5. PIN code
When the function is activated, a four digit PIN code is
requested each time the remote control is switched on. The
first time the code is 0000. When the wrong PIN code is stated
4 times in succession the hydraulic unit is locked A PUK code
(provided by Husqvarna) must then be stated to unlock the
unit.
The display shows: PIN code and ON or OFF.
To activate or deactivate:
Press OK to switch between ON and OFF.

6. Basic setting

This function restores all the menu settings to the factory
settings. The PIN code is also restored.
The display shows: DEFAULT SETTING and ON or OFF. OFF
is shown when a change has been made that differs from the
default settings.

7. Out settings

This function confirms or rejects all settings made before the
operations menu is shown again.
Press OK when the display shows OUT SETTINGS.
The display shows: SAVE? NO.
To not implement the made settings:
Confirm with OK".
To implement the made settings:
Press arrow up/down to select YES.
Confirm with OK".
– 17