Operation And Checkout - Honeywell VBN Instrucciones De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

S3
Fig. 21. Wiring for model with aux./end switches.
24 VAC
1
1
24 VAC
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
HOT
COM
+
1
24 VAC
1
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
SET SWITCH TO MODULATING.
3
Fig. 22. MS7505 with Proportioning controllers operating
multiple actuators (Modulating mode setting).
NOTE: All identified parts except for the valve body and
aluminum valve stem coupler are included in
Replacement Kit (part no. 5112-11).

OPERATION AND CHECKOUT

Once both the mechanical and electrical installations are
complete:
1. Cycle the actuator to verify that the direction of rotation
suits the control sequence.
2. If the rotation direction is incorrect:
S2
S1
M35813
ACTUATOR
2
1
V
2
3
OR +
OR N/A
4
5
FEEDBACK
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
Fltg, fwd
Fltg, rev
ACTUATOR
1
V
2
2
3
OR +
OR N/A
4
5
FEEDBACK
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
Fltg, fwd
Fltg, rev
M34978
VBN CONTROL BALL VALVES AND ACTUATORS
a. For 2-position control actuators: Remount actuator
on the bracket.
b. For floating control actuators: Reverse two control
signal wires (CW/CCW).
c. For analog control actuators either:
(1) Reposition reverse/direct acting switch, or
(2) Remount actuator on the bracket.
d. For modulating control actuators, reposition reverse/
direct acting switch 1.
3. If the control scheme requires fail-safe operation,
ensure that, upon removal of power, the fail position
coincides with the control sequence.
4. If the fail safe position is incorrect, remove and reinstall
the actuator in the opposite orientation as follows:
a. Loosen the shaft coupling bolt using a 10 mm
wrench.
b. Loosen all other mounting bolts connecting the
actuator to the mounting bracket, and set aside.
c. Remove the actuator from the valve shaft.
d. Move the actuator coupling to the opposite side of
the actuator, as displayed in Fig. 23.
(1) Remove the retainer clip from the shaft coupling
and set it aside for later use.
(2) Remove shaft coupling from one side of the
actuator.
(3) Replace the shaft coupling on the opposite side
of the actuator, aligning it based on the stroke
labelling.
(4) Replace the retainer clip on the shaft coupling
using the groove of the coupling.
e. Reconnect the actuator to the valve mounting
bracket by replacing the screws previously removed
(step b)
f.
Tighten the shaft coupling bolt using a 10 mm
wrench.
Fig. 23. Mounting shaft coupling to actuator
7
M19579A
opposite side.
62-2025EFS—04