ELECTRICAL WIRING
WARNING: check that the power sup-
ply is disconnected before perform-
ing operations on the unit.
The unit must be connected directly
to an electrical outlet or to an inde-
pendent circuit.
Provide a 230V (±10%) power supply.
To protect the unit against short cir-
cuits, fit a circuit breaker of max.
2A 250V to the power line with a
Electrical wiring
FCW213VN
FCW212VN
FCW313VN
FCW312VN
FCW413VN
FCW412VN
FCW21VLN
FCW31VLN
FCW41VLN
48
IFCW3LJ 1207 - 5375700_00
Front panel
Power supply terminal block
Base
minimum contact opening distance
of 3 mm.
The electrical power cable must be of
the H07 V-K or N07 V-K type with
450/750V insulation rating if inside
a tube or conduit. Use cables with
double H5vv-F type insulation for
exposed cable installation.
Follow the wiring diagram supplied
with the equipment and shown in this
FCW213V
Motor
FCW212V
FCW21VL
Terminal block
FCW313V
FCW312V
Connection
FCW31VL
cable
Motor
FCW413V
FCW412V
Terminal block
FCW41VL
Connection
cable
Motor
Terminal block
Connection
cable
Cable cross section
Motor
Terminal block
WARNING
The unit must be correctly earthed; incorrect con-
Connection
nection could result in electric shocks or fi res.
cable
document when making the connec-
tions.
Ensure that the installation is wired in
compliance with the laws and stand-
ards in force, and with the instruc-
tions in this manual.
All the parts and materials supplied on
site must comply with the local laws
and regulations.
FCW_2V
FCW_3V
FCW_VL
IG
Microprocess-
or controller
Terminal block
Connection
cable
Microprocess-
or controller
Terminal block
Connection
cable
FCW_2VN
FCW_3VN
FCW_VLN
2A
2
1.5mm