2 Stop generators, after some seconds restart again.
3 Wait 2 minutes and then connect again the device in generator.
If the overload protector trips again after connecting the devices, do not plug the
device. The plugged device may have a problem or exceeds the generator's
power.
NOTE: Once you verify that the generator cannot support or accept the
load, please do not insist. Regular overloads may affect the group despite all of
its advanced protections.
Remember that many types of equipment need extra consumption for startup.
Equipments that use an engine such as compressors, water pumps, circular
saws or others consume up to 3 times more power for startup. For example, a
500W water pump will need 1500W to start up, therefore we would need a
generator no less than 1500W.
(RED) OVERLOAD INDICATOR LIGHT
Upon starting the engine it is completely normal for the (red) overload indicator
light and the (green) output indicator light to turn on at the same time for a few
moments. The overload indicator light will shut down after a few moments and
only the 230V current output will remain on.