6.2 Equipment overload and reassembly

In case of an overload the "BREAKER" will switch to the "OFF" position,
disconnecting the voltage output.
In case of overload, first unplug any plugged equipments from the generator.
Once the equipments are unplugged, assemble the overload protector again,
going to the "ON" position, your machine can bear two types of breakers:
 Breaker lever, turn the lever up (position ON)
 Breaker button, press the button inwards (ON position)
NOTE: The view corresponds to the model GUARDIAN S6-SOL, in other models
the control panel, may vary slightly
If the overload protector trips again after connecting the devices, do not plug the
device. The plugged device may have a problem or exceeds the generator's power.
NOTE: Once you verify that the generator cannot support or accept the load,
please do not insist. Constant overloads may negatively affect the group.
Remember that many equipments need extra consumption for start up.
Equipments that use an engine such as compressors, water pumps, circular saws
or others consume up to 3 times more power for start up. For example, a 1000W
water pump will need 3000W to start up, therefore we would need a generator no
less than 3000W.