6.3

Activate Total Chlorine Monitoring

1. Enter the Technician Menu (by pressing scroll and up and down together)
2. Scroll to " Total Chlorine ON/OFF"
3. Change to "ON" (the default is - OFF)
4. Locate the LCD displays in the HydroGuard control panel. A number should appear in the display
(TCl - 0.00)
Setting Total Chlorine Ratio (Testing Interval)
1. Press Scroll to enter the operator menu
2. Press up and down together to go to the Technician Menu
3. Scroll to "Chlorine Ratio"
4. Set the Chlorine Ratio according to how often you want to measure TC
5. The ratio may be set between 1 and 30
6. Example: If the ratio is 1, a TC measurement will be taken every time a FAC measurement is made (i.e.
every 4 minutes); if the ratio is set to 10, a TC measurement will be taken after 10 FAC measurements
are made (i.e. every 40 minutes).
Setting High Combined and Total Chlorine Alarms
1. Enter the Operator Menu by pressing Scroll
2. Scroll until "Total Chlorine High Alarm" is reached
3. Press Enter
4. Enter Password
5. Select the High Total Chlorine Alarm Level, using the up and down buttons
6. Press Enter
7. Press scroll again – Display should read "Combined Chlorine High Alarm"
8. Press Enter
9. Select the High Combined Chorine Alarm Level, using the up and down buttons
10. Press Enter
11. Press Esc, to return to normal operation
Troubleshooting Specific to Total Chlorine
The troubleshooting of the HydroGuard controller with total chlorine will be the same as the troubleshooting
of the standard HydroGuard controller. However, there are a few conditions that may exist with the total
chlorine controller that do not occur with the standard unit.
62