Normativa - Fanox SIA B Manual De Usuario

Tabla de contenido

Publicidad

7.3.

Normativa

1. EMC requirements
- Emission
1.1. Radiated emission
1.2. Conducted emission
- Immunity
1.3. 1MHz damped oscillatory
waves
1.4. Electrostatic discharge
1.5.
Radiated
radiofrequency
electromagnetic fields
1.6. Electrical fast transients
1.7. Surge
1.8.
Conducted
disturbance
induced by radio frequency fields
1.9.
Voltage
dips,
interruptions and voltage variations
1.10. Ripple on DC input power
port
1.11. Power frequency magnetic
field
1.12. 100KHz damped oscillatory
waves
1.13. Pulse magnetic fields
www.fanox.com
IEC 60255-26
EN 55022
EN 55011
IEC 60255-26
EN 55022
EN 55011
IEC 60255-26
IEC 61000-4-18
IEC 60255-26
IEC 61000-4-2
IEC 60255-26
IEC 61000-4-3
IEC 60255-26
IEC 61000-4-4
IEC 60255-26
IEC 61000-4-5
IEC 60255-26
IEC 61000-4-6
short
IEC 60255-26
IEC 61000-4-11
IEC 61000-4-29
IEC 60255-26
IEC 61000-4-17
IEC 60255-26
IEC 61000-4-8
IEC 61000-4-18
IEC 61000-4-9
Rev. 20
Radiated emission limit for Class A (group 1
for EN 55011) on Enclosure port. Frequency
range
30MHz
-
230MHz
40dBμV/m). Frequency range 230MHz -
1000MHz (Quasi Peak 47dBμV/m)
Conducted emission limit for Class A (group 1
for EN 55011) on Auxiliary power supply port.
Frequency range 0.15MHz – 0.5MHz (Quasi
Peak 79μV, Avg 66μV). Frequency range
0.5MHz – 30MHz (Quasi Peak 73μV, Avg
60μV)
Class
3,
Repetition
frequency
Duration
of
each
application
Common mode for all terminals ±2.5kV.
Differential mode for all terminals excepts
Communication port ±1kV
Level
4,
Contact
discharge
discharge ±15kV
Level 3, Test field strenght 10V/m, Frequency
80MHZ - 1000MHz and 1400MHz - 2000MHz,
AM
Modulation
80%
for
sinusoidal signal
Level 4, Power supply to Earth terminals
±4kV, Signal and control terminals ±2kV.
Repetition frequency 5KHz, Burst duration
75s.
Level 4, Line to earth for all terminals ±4kV.
Line to Line for all terminals excepts
Communication port ±2kV
Level 3, Applied voltage 10V, Frequency
0.15MHz - 80 MHz, AM Modulation 80% for
1KHz carrier sinusoidal signal, Dwell time 1s.,
Test duration >10s.
DC Voltage Dips: 40%, 130ms and 70%,
100ms,
3
times
DC Voltage Interruption: 100ms, 3 times
every 10s.
Level 4, Ripple 15%, 50Hz and 100Hz
Level 5, Continuous field strenght 100 A/m.
Short field strenght for a duration of 3s. 1000
A/m. Frequency 50Hz.
Class 3, Repetition frequency 40Hz, Duration
of each application 3s.
±2.5kV. Differential mode: ±1kV
Field strenght 1000 A/m, Cadence between
pulses 40s.
(Quasi
Peak
400Hz,
3s.
±8kV.
Air
1KHz
carrier
every
10s.
Common mode:
69/123