The first step in the electrical configuration is to place the correct battery bank,
with its correct connection configuration and connected according the
manufacturer's specifications, thus obtaining the right voltage and capacity for
the installation to be carried out.
Different types of batteries exist. In the case of domestic hybrid wind energy/
solar energy installations, open lead-acid batteries are recommended and, to
meet the installations charge capacities, certain minimum installation
requirements are essential to assure correct running and durability of the
installation.
The minimum installation recommendations and battery-to-regulator cable
recommendations are the following:
Model
Bornay 600 / 12V
Bornay 600 / 24V
Bornay 600 / 48V
Bornay 1500 / 24V
Bornay 1500 / 48V
Bornay 3000 / 24V
Bornay 3000 / 48V
Bornay 6000 / 48V
CAUTION:
The use of stationary open lead-acid
batteries is recommended.
With the correct battery selected and assembled in the installation, the regulator
must now be installed on the wall. This is fixed using the four holes (two upper
and two lower) located in its metallic casing. Fixing is achieved using long
screws and plastic plugs.
Battery Cable
16 mm
2
16 mm
2
10 mm
2
25 mm
2
16 mm
2
35 mm
2
25 mm
2
50 mm
2
Bornay 600 – Rev 6.0 - P 47
Minimum battery size
550 Ah C
250 Ah C
150 Ah C
660 Ah C
350 Ah C
1100 Ah C
600 Ah C
1200 Ah C
 WARNING:
Use of the wrong battery can cause
irreparable damage to your wind
turbine.
100
100
100
100
100
100
100
100