Double check that the wind turbine is totally braked and disconnects the
wires from the wind turbine.
Disconnect the positive cable from the battery.
Lastly, disconnect the negative cable.
Once the batteries have been installed and connected to the regulator, we will
move on to the wiring between the regulator and the tower top of the tower
where the wind turbine will be installed.
To minimize wire loss, the distance between the wind turbine and the regulation
control box must be as short as possible. Never longer than 100 meters.
To determine the base connection cable gauge for use in line with the
characteristics of the wind turbine and its distance from the control box, see the
following table for copper conducting wire:
Model
Bornay 600 / 12v
Bornay 600 / 24v
Bornay 600 / 48v
Bornay 1500 / 24v
Bornay 1500 / 48v
Bornay 3000 / 24v
Bornay 3000 / 48v
Bornay 6000 / 48v
The following table shows conversions between gauges in mm2 and AWG, as
well as the corresponding diameters for these gauges in mm and inches.
mm
section
2
AWG section
Diameter (mm)
Diameter (in)
Iac x fase
0-20
(A)
mts
17
10 mm
8.8
6 mm
4.5
4 mm
22
10 mm
11
6 mm
42
10 mm
21
4 mm
42
6 mm
4
6
11
9
2.26
2.76
3.57
0.088
0.108
0.141
Bornay 600 – Rev 6.0 - P 50
20-40
40-60
mts
mts
16 mm
25 mm
2
2
2
10 mm
2
16 mm
6 mm
10 mm
2
2
16 mm
25 mm
2
2
2
10 mm
2
16 mm
16 mm
25 mm
2
2
2
6 mm
2
10 mm
10 mm
16 mm
2
2
10
16
25
7
5
3
4.51
5.64
0.178
0.222
60-80
80-100
mts
mts
35 mm
50 mm
2
2
2
25 mm
2
35 mm
16 mm
25 mm
2
2
25 mm
35 mm
2
2
2
25 mm
2
35 mm
35 mm
50 mm
2
2
2
16 mm
2
25 mm
25 mm
35 mm
2
2
35
50
1
0
6.68
7.98
0.263
0.314
2
2
2
2
2
2
2
2