FORCE B
TEST mode activation
Reach the screen shown in fig. 61, navigating the following menu path: "USER MENU
Test mode".
The boiler will light, gradually reaching the maximum heating power (Range Rated) set as described in the next section.
The display will show the actual heating power and that set.
Press the contextual buttons 1 and 2 to increase the maximum power.
To deactivate the TEST mode, press the contextual button 3.
The TEST mode is automatically disabled in any case after 15 minutes.
After activating test mode, to exit the TEST make sure to deactivate the function, only by pressing the contex-
A
tual button "Stop Test".
DO NOT TURN OFF THE BOILER ELECTRICALLY DURING THE TEST.
If that happens, when the power is switched on again the system does not recognise deactivation of the TEST,
and starts working as though still in TEST mode and not as in a normal heating demand.
EN
fig. 60- Models FORCE B 120 and FORCE B 150
Installer Test Mode
12%
80%
CURRENT
1:
Stop Test
Save CH max
fig. 61 - Test mode (example heating power = 80%)
cod. 3541T170 - Rev. 00 - 09/2019
F G
Maintenance
RANGE RATED
E
Test Mode
155