3.3 Troubleshooting

The burner is equipped with an advanced self-diagnosis system. In case of a burner fault, the display (detail 4 - fig. 1)
flashes indicating the fault code.
There are faults the cause permanent shutdowns (marked with the letter "A"): to reinstate operation, press the "Reset"
button (detail 8 - fig. 1) for 1 second; if the burner fails to restart, it is necessary to firstly eliminate the fault.
Other faults cause temporary shutdowns (marked with the letter "F") which are automatically reset as soon as the value
returns within the burner's normal operating range.
Table. 5 - List of faults
Fault
Fault
A01
No ignition shutdown
F02
Parasite flame elimination
A02
Shutdown for parasite flame
A03
Wiring fault
A04
Auger safety thermostat block
F05
Incorrect pipe pressure adjustment
Pressure transducer fault (discon-
F06
nected)
F10
Boiler shell probe fault (if enabled)
F11
DHW sensor fault
F14
Card parameter fault
F34
Supply voltage under 170V.
F37
Card parameter fault
F42
Card parameter fault
EN
Cause
Pellet container empty
Auger cable broken or disconnected
Faulty igniter resistance
Combustion head dirty
Pellet feed duct obstructed
The demand for heat has ended, but the
burner detects flame
Incorrect ignition parameters
Photoresistance short circuit
Extraneous light strikes the photoresistance
Incorrect ignition parameters
Jumper of terminals 20-21 not connected
Boiler under pressure
Faulty safety thermostat
Auger cable broken or disconnected
Pressure sensor connection tube squashed
Fan motor damaged
Fan dirty
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
Wrong card parameter setting
Electric mains trouble
Wrong card parameter setting
Wrong card parameter setting
cod. 3541F710 - Rev. 00 - 05/2017
Cure
Fill the container with pellets
Restore the connection
Replace and empty the head of pellets
Empty and clean it
Free it, make sure the combustion head is
not clogged and empty it if necessary
Wait for end of post-ventilation
Check ignition parameters
Replace the photoresistance
Eliminate the light source
Check ignition parameters
Check the wiring
Clean it and check correct minimum flue
draft (10Pa)
Replace it
Restore the connection
Replace
Replace
Clean it
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the card parameter and modify it if
necessary
Check the electrical system
Check the card parameter and modify it if
necessary
Check the card parameter and modify it if
necessary