ECOTRONIC tech
Assigning terminals
The controller can work with 4 different types of circulating pumps:
Conventional circulating pump (Not High Efficiency)
230Vac output characteristics:
S olar circulating pump output triac rated current= 16A (max. permissible load: 0.5A 230Vac cos φ 1)
A UX1 output relay rated current= 5A@250Vac (max. permissible load: 0.5A 230Vac)
A UX2 output relay rated current= 5A@250Vac (max. permissible load: 0.5A 230Vac)
F REE CONTACT output relay rated current= 10A@250Vac, 5A@30Vdc (max. permissible load: 0.5A 230Vac)
High Efficiency circulating pump (WILO Yonos Para series)
For PWM versions (without selector) it is necessary to connect the circulating pump signal cable supplied.
For RKC versions (with selector) it is not necessary to connect the circulating pump signal cable supplied.
230Vac output characteristics:
S olar circulating pump output relay rated current= 5A@250Vac (max. permissible load: 0.5A 230Vac)
A UX1 output relay rated current= 5A@250Vac (max. permissible load: 0.5A 230Vac)
A UX2 output triac rated current= 16A (max. permissible load: 0.5A 230Vac cos φ 1)
F REE CONTACT output relay rated current= 10A@250Vac, 5A@30Vdc (max. permissible load: 0.5A 230Vac)
High Efficiency circulating pump (WILO Stratos Para series)
It is necessary to install a relay to feed the circulating pump.
Installation of the relay will be by the customer and must meet the minimum requirements: contact rated current
>= 8A, rated voltage 250VAC, Contact material AgSnO2 or Ag/Ni 90/10.
Protection with fuse: 10/16 A, delayed or automatic fuses with characteristic C.
230Vac output characteristics:
S olar circulating pump output relay rated current= 5A@250Vac (max. permissible load: 0.5A 230Vac)
A UX1 output relay rated current= 5A@250Vac (max. permissible load: 0.5A 230Vac)
A UX2 output triac rated current= 16A (max. permissible load: 0.5A 230Vac cos φ 1)
F REE CONTACT output relay rated current= 10A@250Vac, 5A@30Vdc (max. permissible load: 0.5A 230Vac)
NOTE
Every circulating pump requires a specific parameterization and wiring.
Pay attention to the following paragraphs.
Stratos Para
112
Yonos Para RKC
cod. 3540V011 - 03/2017 (Rev. 00)
Yonos Para PWM
EN
Conventional