SinePower
9.5
Connect multiple appliances
The device is equipped at delivery with galvanic isolation. For the safe operation of
multiple appliances, it is essential that a circuit breaker (residual current circuit
breaker) is built into the socket distribution circuit, see sample circuit diagram in
fig. 6, page 5.
Sample circuit diagram legend:
No. in
fig. 6,
Explanation
page 5
1
230 Vw power source
2
additional devices, e.g. battery charger, refrigerator
3
DC power source (battery)
4
Inverter
5
Set grounding bridge (At delivery: not set, shown by dotted line)
6
Circuit breaker (residual current circuit breaker)
7
Socket distribution circuit for appliances
!
WARNING! Danger of electrocution!
If you wish to connect more than one appliance to the inverter and install
a socket distribution circuit, you must arrange a circuit breaker (residual
current circuit breaker) and set a grounding bridge in the inverter.
➤ Install a residual current circuit breaker in the socket distribution circuit.
Setting the earthing bridge (fig. 5 5, page 4)
9.6
➤ Remove the earthing screw from the bottom hole.
➤ Screw the screw into the top hole.
EN
Connecting the inverter