Aros 10000P Manual De Instrucciones página 100

Inversor fotovoltaico paraconexión en red
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Error Message
ERR MICROS
OVERTEMPERATU
RE
ERR FAN
ERR AC RELAY
HIGH DC LEVEL
ERR EEPROM
ERR COM
HIGH DC BUS
LOW DC BUS
ERR DC SENSOR
ERR GFCI
Page 100
- ENGLISH -
Error definition
The readings of the 2
microprocessors
inconsistent
The detected temperature
is high
The cooling fans are not
able to spin
The
output
relays
behaving abnormally.
The continuous component
of the current sent to the
grid is too high.
The EEPROM memory is
abnormal
Communication
between
the two microprocessors is
abnormal
The inverter capacitator set
voltage is too high.
The inverter capacitator set
voltage is too low.
The DC sensor at output is
abnormal
The GFCI detection circuit
is abnormal
Possible Action
1. Please check the system satisfies the
requirements of paragraph 5.3
2. Check the quality of ground connection of
inverter
3. Check
that
complies with the requirements of chapter
5.4
4. Check whether high distorting loads are
are
present on the system and that any
capacitive power factor correctors have
insertion resistors or electronic insertion
circuitry.
5. Ensure
the
especially around zero crossing, on grid
voltage. It is possible to use either an
oscilloscope or a grid analyzer
6. Reboot the inverter
1. Protect the inverter from direct sunlight
2. Reduce the ambient temperature by some
other means or move the inverter to cooler
place
3. If the above action does not solve the
problem, please call your local dealer
Check that no scrap, dirt or bugs are blocking
the cooling fans.
are
1.
Disconnect BOTH PV (+) and PV (-)
2.
Wait for a few seconds
3.
Once the display has switched off, then
reconnect.
4.
Repeat points from 1to 3Leaving the
inverter to cool down while off.
5.
If the message reappears, please call
your local dealer
the
ground
connection
absence
of
transients,

Publicidad