NOTE:
For UL Residential Burglary (UL1023), Home Health Care (UL1637), ULC Residential
Burglary (ULC/ORD-C1023) installations, the maximum Supervision window shall be set to 24
hours.
For UL Residential Fire (UL985) installations, the maximum supervision window is set to 200s.
For UL Commercial Burglary (UL1610/UL365) and ULC Residential Fire (ULC-S545), the maxi-
mum supervision window shall be set to 4 hours.
[804][810] Wireless Option 1
To program wireless options:
1. Enter Installer Programming section [804][810].
2. Select one of the following options by scrolling or entering the hotkey:
Table 8: Wireless Options
On: the system cannot be armed if a wireless supervisory trouble
01
RF Delinquency
exists. An RF delinquency trouble is generated.
Off: wireless supervisory troubles do not prevent arming.
On: if a supervisory or jamming trouble occurs during Away arming,
Wireless Supervi-
the siren activates and the event is logged and reported.
02
sory/ RF Jam Alarm
Off: supervisory or RF jam troubles during Away arming do not acti-
vate the siren or get logged and reported.
On: module tampers are logged and reported.
03
Module Tamper
Off: module tampers are not logged or reported.
On: fire devices are supervised every 200 seconds. If the device fails
to report within this window, a supervision trouble is generated.
Off: fire devices follow the supervision window programmed in sec-
04
Fire Supervision
tion 802, up to a maximum of 18 hours. The supervisory window can
be programmed with a higher value, but detectors still go into fault
after 18 hours.
3. Press [*] to accept the selection and [#] to exit.
[804][841] Visual Verification Programming
To program wireless options:
1. Enter Installer Programming section [804][841].
2. Select one of the following options by scrolling or entering the hotkey:
Table 9: Visual Verification Sub-Sections
001
Visual Verification
002
View Time Window
003
View Other Alarms
[804][901]-[905] Delete Wireless Devices
To delete wireless devices:
1. Enter Installer Programming section [804] then select one of the following sub-sections:
Table 10: Module Label Sub-Sections
Sub-Section
901
Delete wireless zone devices
902
Delete wireless key
903
Delete sirens
On: Alarms trigger image capture from PIR
Cameras
Off: Alarms do not trigger image capture
from PIR Cameras
01 Alarm + 5 Minutes
02 Alarm + 15 minutes
03 Alarm + 1 Hour
01 Fire key enabled/disabled
02 Duress key enabled/disabled
03 Medical key enabled/disabled
04 Panic key enabled/disabled
Description
Table 10: Module Label Sub-Sections
904
Delete repeaters
905
Delete keypads
2. Select a device to delete using the scroll keys or go directly to a specific device by entering a
hotkey.
3. Press [*] to delete or [#] to exit.
[804][921]-[925] Replace Wireless Devices
Use this option to replace a faulty device enrolled on the system with another device of the same type
while maintaining the configuration of the original. The faulty device does not need to be deleted.
To replace a wireless device:
1. Enter Installer Programming section [804] then select one of the following sub-sections:
Table 11: Replace Device Sub-Sections
Sub-Section
921
Replace wireless zone devices
922
Replace wireless keys
923
Replace sirens
924
Replace repeater
925
Replace keypad
2. Press [*] to select a sub-section. The first available device is displayed.
3. Select a device to replace using the scroll keys or go to a specific device by entering a hotkey.
Press [*]. When prompted, activate the device (full enrollment) or enter the device ID (pre-enroll-
ment). A message is displayed confirming enrollment.
[804][990][001 – 005] Show All Devices
Use this section to review wireless devices enrolled on the system and to view serial numbers asso-
ciated with each device.
To review wireless device information:
1. Enter Installer Programming section [804][990] then select one of the following sub-sections:
• [001] – all zones
• [002] – repeaters
• [003] – sirens
• [004] – wireless keys
• [005] – keypads
2. Press [*] to select a wireless device type. The first available device is displayed.
3. Use the scroll keys to view the enrolled devices.
NOTE:
This option is not fully supported by LED and ICON keypads.
[904] Placement Testing Wireless Devices
This test is used to determine RF signal status for wireless devices and can be performed at a system
keypad or at the individual device. These instructions pertain to testing at the keypad. For instruc-
tions on placement testing at the device, refer to the installation sheet provided with the wireless
equipment. The following test modes are available:
Table 12: Wireless Device Placement Test Modes
001-128 Test wireless zones
Test wireless devices individually by zone.
Test each enrolled wireless repeater.
520
Test all repeaters
521-528 for repeaters 1-8
Test each enrolled wireless siren.
550
Test all sirens
551-556 for sirens 1-16
Test individual wireless keys. Once in this section, press a button
600
Test all wireless keys
on the wireless key to begin the test.
601-632 for wireless keys 1-32.