II.8.3.6 Checks to be made while the machine is running
Cut-in test:
use the water intercept valves to reduce
the flow to the evaporator.
START
Ask all unauthorised personnel
to leave the area.
YES
Is the water differential
pressure switch activated
correctly?
YES
Is the working pressure
reading correct?
YES
If you take the pressure on the
high pressure side to approx. 8
bar, are there gas leaks of > 3
grams/year?
NO
Does the unit display feature
any alarms?
NO
Start-up procedure completed!
42
SECTION II: INSTALLATION AND MAINTENANCE
NO
Check and/or replace the component.
Stop the unit and check the cause of
NO
this anomaly.
Stop the unit and check the cause of
YES
the leak (EN 378-2).
Check the cause of the alarm.
YES
See table of alarms.