Service switch/Manual adjusting switch
The service switch and the manual adjusting switch
are used to adjust the servomotor manually; see
section
12.2.5 Operating the servomotor
1
2 3
Fig. 13
Service switch/Manual adjusting switch
Item
Description
1
Service switch
2
Position "Auto" (standard)
Position "Manual" (only for adjusting the
3
servomotor manually)
Manual adjusting switch (on outside of
4
housing)
"-" (servomotor moves in the direction
5
"close/min.")
"+" (servomotor moves in the direction
6
"open/max.")
12.2.2 Reprogramming the setpoint range, final
positions and control direction
Setpoint range
In the factory settings, the setpoint range is set to
4-20 mA.
To change from 4-20 mA to 0-20 mA:
1. Disconnect the power to the servomotor.
2. Hold the SET and R buttons down.
3. With the buttons held down, switch the supply
voltage on.
To change from 0-20 mA to 4-20 mA:
1. Disconnect the power to the servomotor.
2. Hold the SET and L buttons down.
3. With the buttons held down, switch the supply
voltage on.
18
manually:
4
5
6
Final positions
In the factory settings, the left (max.) final position is
set to 100 % stroke at 20 mA and the right (min.)
final position to 0 % stroke at 4 (0) mA.
To reprogram the left final position:
1. Set the Man/Auto DIP switch to "Man".
2. Use the L/R buttons to approach the required left
final position.
3. Press the SET button (blue LED flashes) and then
press the L button within 3 seconds.
– The newly set left (max.) final position at 20 mA
has now been programmed.
To reprogram the right final position:
1. Set the Man/Auto DIP switch to "Man".
2. Use the L/R buttons to approach the required
right final position.
3. Press the SET button (blue LED flashes) and then
press the R button within 3 seconds.
– The newly set right (min.) final position at
4 (0) mA has now been programmed.
Effective control direction
In the factory settings (or after the final positions
have been programmed), the left final position is set
to 100 % stroke (or the newly programmed max. final
position) at 20 mA and the right final position to
0 % stroke (or the newly programmed min. final
position) at 4 (0) mA.
To reverse the effective control direction to 0 (4) mA
at the left final position and 20 mA at the right final
position:
1. Set the DIP switch to the "inv" (inverse) position.
To reset the effective control direction to 20 mA at
the left final position and 0 (4) mA at the right final
position:
1. Set the DIP switch to the direction opposite to
"inv" (not inverse).
Completing programming work
1. To complete programming work,
set the Man/Auto DIP switch to "Auto".
2. Close the hood again and tighten the hood
screws.

12.2.3 Error message

Error message output: Terminals 56, 57
Maximum permissible load: 125 V
Red LED lights up if a contact is open.
The error message contact opens in the following
instances:
If there is a setpoint violation: I
mode 4-20 mA).
If the "Manu/Auto" switch is set to the "Manu"
position (controller in programming mode).
If there is no operating voltage.
< 4 mA (only in
set