OPERATING INSTRUCTIONS (XE-70M CONTROLLER)
Active Protocol – Allows the serial port to be configured
to Airbus (used for X-Series system controllers and
integral sequencing) or Modbus protocols��
MODBUS Address – Sets the modbus node ID for the
controller to communicate with a Modbus capable
device, this can be any value between 1 and 254��
RS-485 Address – Sets the airbus address that allows the
controller to communicate over Integral Sequencing or
an X-Series system controller network��
Pages 5 & 6 – Ethernet Settings (ECO Module Only)
Please note that these pages will have no effect unless
the ECO module option has been purchased��
Figure 21 : Ethernet Settings (ECO Module Only)
IP Address Setting – When DHCP is not enabled, this
setpoint sets the IP address of the controller��
IP Address Actual – This will match the IP address setting
when DHCP is not enabled�� If DHCP is enabled this will
display the address assigned to the controller by the
DHCP server��
Default Gateway Setting – Setpoint for the default
gateway��
Default Gateway Actual – Current reading/setting for
the default gateway��
Subnet Mask Setting – Setpoint for the subnet mask
Subnet Mask Actual – Current reading/setting for the
subnet mask
MAC Address – This is the unique hardware MAC address
for the controller�� This can not be changed��
Enable DHCP – Allow the controller to automatically
receive an IP address from the Local Area Network (LAN)
Apply– After editing the desired setpoint navigate to the
accept setting and press enter in order for the values in
the setting variables to be confirmed by the controller��
Cancel – Discard any changes made to the Ethernet
settings��
80448418 Rev.C
RELEASED 20/Jul/2016 17:56:55 GMT
INTEGRAL SEQUENCING FOLDER
Figure 22 : Integral Sequencing folder
Integral Sequencing allows the compressor to be
networked with up to three other compressors (fixed or
variable speed) to maintain a stable system pressure by
loading and unloading compressors as needed�� Integral
sequencing requires no additional hardware other than
a serial two wire connection daisy chained between all
compressors in the system, connected to port X04 on the
controller��
For a compressor to be a member of the integral
sequencing system, the COM control setpoint in
the operator settings tab must be enabled and the
compressor must be started via the local start button��
Additionally, it is recommended that the Auto-Restart
function be enabled as the integral sequencing system
1