OPERATING INSTRUCTIONS (XE-70M CONTROLLER)
Airend Discharge Temperature – The temperature of
•
the air/oil mixture at the discharge of the compression
module��
After-cooler Discharge Temperature ( Not available
•
on this compressor model) – The temperature of the
air after passing through the After-cooler�� Note that
this will only be shown if the Low Ambient option has
been purchased and installed��
After-cooler Discharge Pressure (integrated dryer
•
units only) ( Not available on this compressor
model) – Pressure the compressor is delivering before
the dryer��
Page 2 – Compressor Data
Figure 24 : Compressor data
Compressor Data:
Power ON Hours – The number of hours the controller
•
has been powered up
Running Hours – The number of hours the
•
compressor's motor has been running
Loaded Hours - The number of hours the compressor
•
has been producing air
Real Time Clock - Current time of day
•
Pages 3 and 4 – Digital Inputs
Figure 25 : Digital inputs
80448418 Rev.C
RELEASED 20/Jul/2016 17:56:55 GMT
Digital Inputs:
Each digital input will have an indication showing
whether the input is in an "OPEN" or "CLOSED" state�� This
is the physical state of the input and may not necessarily
line up with the logical condition�� The normal state is
shown below��
Emergency Stop – Normally Closed
•
Main/Fan Motor Overload – Normally Closed
•
Remote Load Enable – Normally Open
•
Remote Load/Unload – Normally Open
•
Remote Start - Normally Open
•
Remote Stop – Normally Closed
•
Dryer Temperature Fault – Normally Open
•
Dryer High Pressure – Normally Closed
•
Pages 5 and 6 – Digital Inputs
Figure 26 : Digital inputs
Digital Outputs:
Each digital output will have an indication showing
whether the output is in an "OPEN" or "CLOSED" state�� This
is the physical state of the input and may not necessarily
line up with the logical condition�� The normal state is
shown below��
Starter Contact KM1, KM2 – Normally Open
•
Starter Contact KM3 – Normally Open
•
Fan Starter Contact KM4 – Normally Open
•
Load Solenoid 1SV – Normally Open
•
Modulation Solenoid 3SV – Normally Open
•
Dryer Run / Fan Run – Normally Open
•
PORO Horn – Normally Open
•
Trip Indication – Normally Open
•
1