④
Mounting
base
Pillar nut
Leave
0.197 in.
mounting base and pillar nut
⑥
Screw the coupling nut
onto the valve stem until
the pillar edges rest on the
mounting base
⑧
Lock the coupling nut
⑩
Drive the coupling up or down, until the edges of
the pillars rest on the mounting base
⑪
Tighten the pillar nuts
6
⑤
appr. 0.197 in.
Move the coupling down until it hits the valve stem.
Continue moving until there is a 0.197 in. gap
gap between
between the pillar end and the mounting base
⑦
Repeat ⑤ and ⑥ until the valve stem is screwed
0.47 in. (M8 to M12) resp. 0.63 in. (M14 and larger)
⑨
Tighten the clamping screws crosswise with 70.81 lbf in.
or
In case of any question, please do not hesitate to contact us:
Pillar end
Mounting
base
⑤
+
⑥
into the coupling nut by
70.81 lbf in.
WRONG
Phone: +49 (0) 6322 / 6003 ‐ 0
Mail: info@ps‐automation.com
appr.
0.197 in.
0.47 in. (M8, M12) /
0.63 in. (> M14)
CORRECT