INSTALLATION
INSTALLING THE UNIT
To install the unit, proceed as follows:
- Remove the air filter
- Remove the covering cabinet
- With wall-mounted units, keep a mini-
mum clearance of 80mm from the
floor. With floor-standing units on feet,
refer to the instructions supplied with
the accessory
- Use wall plugs (not supplied) for wall-
mounted installations
When using the support accessory (AMP
accessory), proceed as follows:
Assemble the 4 supports at the sides of
the device, inserting the upper tang in the
hole and fixing the lower part to the com-
ponent by means of the screws supplied.
Fix the flanges to the ceiling, using wall
plugs (not supplied); for the relative
positions between the flanges and the
component, refer to the size data
- Apply any accessories.
The VCF valve and the BC4 tray cannot
be installed at the same time on the
same fan coil.
M a k e t h e wa t e r c o n n e c t i o n s a s
described in the relative chapter.
Make the condensate discharge connec-
tion as described in the relative chapter.
WATER CONNECTIONS
- Make the water connections.
- In the event of disassembly and rein-
stallation, use new gaskets.
Refer to the size data for the position,
type and diameter of the water con-
nections.
You are advised to adequately insulate
water lines and/or fit the auxiliary
condensate drain tray (available as an
accessory), to prevent dripping during
CONDENSATE DRAIN
In the event of horizontal installation,
assemble the condensate discharge
connection
supplied.
Make sure you
seal the connection between the drip
tray and the fitting with silicone. The
condensate drain network must be
properly scaled and the piping situ-
ated in such a way as to keep an ade-
quate slope along the route (min. 1%).
The fan coils that work in heat mode
only do not require condensate dis-
charge.
Make the electrical wiring as shown in
the relative chapter and in the wiring
diagrams.
Install and connect any accessories.
Complete the installation by reassem-
bling the casing and air filter.
Start up the fan coil and check all the
components and functions are operat-
ing correctly.
ZX
65 mm
the cooling function.
After installing, check the seal on the
connections.
If condensate is discharged into the
sewage system, install a siphon to
prevent the return of unpleasant odours
into the room.
Carry out a functioning and seal test of
the condensate drain system by pour-
ing water into the tray
1
FCXI_AS
B
A
Ø est. 20,5mm
IFCXIUASLJ 1210 - 5383600_04
2
FCXI_U
AMP
FCXI_U
B
B
A
A
17