4. Mini Bio/Mini Bio Luxury boiler design... | 5. Design guidelines
Fig. Oxygen sensor connection (Mini Bio Luxury)
5. Design guidelines
The installation and all connections must comply
with the relevant standards and regulations!
5.A Burner location requirements
The distance of boiler walls and accessories from the room walls must
guarantee easy and failure free operation of the hot water boiler (boiler
control system operation, efficient manual fuel feeding to the storage
hopper, repairs, inspections etc.). Ensure sufficient space when
planning and installing the boiler and its accessories in the distance
required to open all boiler doors, clean the combustion chamber and
the exchanger baffles.
The following diagram (see 'Boiler location in the boiler room - dimension
diagram') and the table (see 'Boiler dimension data') shows recom-
mended installation space for the boiler and its accessories.
Experts in heating
Table - Boiler room dimension data
Boiler room dimensions
Marking
unit
A
mm
B
mm
C
mm
D
mm
E
mm
F
mm
Mini Bio and Mini Bio Luxury User Manual - ENGV 08.15
Values
≥ 500
≥ 500
≥ 500
≥ 1000
≥ 2000
≥ 50