3.4 Power Connection
CAUTION
The power connection has to be connected with a 5 wire cable. For security reasons, protective
conductor PE must be connected in any case.
The power supply line must be equipped with an appropriate line protection. For further information
see the Technical Data 5.1. Reducing factors must be taken into account if circuit breakers are
connected in series. Always observe the following standards:
DIN VDE 0298-4
DIN VDE 0100; Part 430 Protective measures: protection of cable and cords against
DIN VDE 0100; Part 410 Protective measures: protection against electric shock
Also observe the following requirements specified by the local network operator:
Pertinent technical and special rules and regulations
The installation approval must be submitted.
CAUTION
Check the line voltage, which may not exceed 265 V (phase against neutral conductor). If
the line voltage is higher than 265 V, contact your local network operator.
Apply the power cable to the supplied connector as illustrated, connect the power cable to
the inverter and fasten the connector.
Note:
Figure 5
28
Risk of electric shock and fire caused by high leakage current!
Before connecting the device to the supply circuit, establish a ground
connection by means of the labeled ground stud!
Types of cable placement and current-carrying capacity
overcurrent
Before connecting the inverter to the AC network, isolate the power
connection, verify that the system is de-energized, and protect the circuit
breaker against reactivation.
When using wire end ferrules with isolating collar, make sure you do not
introduce the insulation of the wire end ferrule into the clamping area of the
terminal.
Power connection