After performing the operations described in the INSTALLATION chapter, the inverter can be started.
-
When STEADYPRES is switched on, it enters the STARTING phase, which lasts 10 seconds, after
-
which STEADYPRES returns to the same operating conditions in which it was when it was last
switched off:
o in WORK mode if at the time of the last shutdown was IN SERVICE
o in OUT OF SERVICE mode if at the time of the last shutdown was OUT OF SERVICE
(OFF)
In case of accidental fall of the power line, if it STEADYPRES was in serivce, when the power returns,
-
it automatically returns in service
- To put STEADYPRES IN SERVICE / OUT OF SERVICE, beat the START / STOP button.
- In applications with parallel inverters (MASTER / SLAVE) is just the MASTER inverter that receives input
from the keyboard
- SLAVE inverters operate independently only if the MASTER is turned off, in which case they receive input
from its own keyboard.
- In each group can be only one MASTER, one SLAVE 1 and one SLAVE 2.
- In normal operation, you can view the status parameters.
For visualization of the operating parameters see
keyboard
the menu INSP (inspection) allows you to view the history of the inverter: the operating hours,
number of starts, alarm recording.
WH
INSP
TH
NS
SH
E1
EH
EE
QUICK INSTALLATION GUIDE
LIGHT SIGNALS
ON
STEADYPRES does not detect power supply. WARNING:
cannot guarantee the absence of power supply, the
electronic board may be faulty, but under tension
STEADYPRES
BY)
STEADYPRES
STEADYPRES
manual
STEADYPRES
INSPECTION MENU
OFF
BLINKING
is live, but the pump is not running (STAND-
is live, and the pump is running
is live, but out of serivce; the re-arm is only
is in ALARM mode, re-arm is only manual