20
Foreman Ductable Dual Fuel Indirect-Fired Heater

Belt Replacement

1. Push the belt tensioner clockwise for removal of the
belt from pulley.
2. Check the fan and motor pulley grooves for dirt,
clean the pulleys if needed.
3. Install new belt.
Belt Tensioner
The belt tensioner automatically applies the proper
tension to the belt during operation, thereby eliminat-
ing the need for manually tensioning the belt during
service.
Belt
Tensioner
Fan and Motor Pulleys
1. Remove belt from pulleys. See Belt Replacement.
2. Loosen allen screw on fan and motor pulleys.
3. Remove pulley and key from fan shaft and motor.
4. When installing new pulley, use a straight edge,
check motor and fan pulley alignment. Contact must
be made at edges of both pulleys.
Owner's Manual • Foreman

Fan Motor

1. Loosen electrical supply access panel screws on
motor
2. Remove access panel and gasket
Motor access
panel
8 x 3/8 (2)
sheet
metal
3. Disconnect power supply wire.
4. Removed the four bolts using a 1/2 inch open
ended wrench.
■ Ensure motor and fan pulleys are properly aligned
when reinstalling.
■ Motor bearings are permanently lubricated.
Gasket
Power lead Terminal
Black .............. 2
White ............. 4
Green ............. Ground