WIKA S-11 Manual De Instrucciones página 19

Transmisor de presión con membrana aflorante
Ocultar thumbs Ver también para S-11:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6. Commissioning, operation
6.2 Electrical mounting
The instrument must be earthed via the process connection.
For instruments with voltage output, use shielded cable, and, if the cables are longer than 30 m or
they leave the building, earth the shield at least at one end of the cable.
In North America, use the instrument in line with "class 2 circuits" or "class 2 power units" in accord-
ance with CEC (Canadian Electrical Code) or NEC (National Electrical Code).
Select a cable diameter that matches the cable gland of the plug. Make sure that the cable gland of
the mounted plug has a tight fit and that the seals are present and undamaged. Tighten the threaded
connection and check that the seal is correctly seated, in order to ensure a tight seal.
For cable outlets, make sure that no moisture enters at the cable end.
Connection diagrams
Angular connector DIN 175301-803 A
2-wire
U
1
+
U -
2
S
-
+
Wire cross-section max. 1.5 mm
Cable diameter 6 ... 8 mm
Circular connector M12 x 1 (4-pin)
2-wire
U
1
+
U
3
-
S
-
+
WIKA operating instructions pressure transmitter, model S-11
3-wire
1
2
3
2
3-wire
1
3
4
Cable outlet, unshielded
2-wire
U
brown
+
U -
green
S
-
+
Wire cross-section 3 x 0.5 mm
Cable diameter 6.8 mm
Cable lengths 1.5 m, 3 m, 5 m, 10 m, 15 m
3-wire
brown
green
white
2
19
GB

Publicidad

Tabla de contenido
loading

Tabla de contenido