Idiomas disponibles

7. Adjustment of zero point ... / 8. Maintenance and cleaning
7.4 Finish the adjustment (figure A)
Disconnect the instrument connector
Carefully push the instrument connector
GB
seals. The seals must be clean and undamaged in order to guarantee the given ingress protection.
Tighten the clamping nut
After the adjustment, check that the system is functioning correctly.
Recommended recalibration cycle: 1 year

8. Maintenance and cleaning

8.1 Maintenance
This pressure transmitter is maintenance-free.
Repairs must only be carried out by the manufacturer.
8.2 Cleaning
CAUTION!
Before cleaning, correctly disconnect the instrument from the pressure supply, switch it
off and disconnect it from the power supply.
Do not use any pointed or hard objects for cleaning, as they may damage the diaphragm
of the process connection.
Clean the instrument with a moist cloth.
Electrical connections must not come into contact with moisture.
Wash or clean the dismounted instrument before returning it in order to protect personnel
and the environment from exposure to residual media.
Residual media in the dismounted pressure transmitter can result in a risk to persons,
the environment and equipment. Take sufficient precautionary measures.
For information on returning the instrument see chapter 10.2 "Return".
22
from the power supply and the display unit.
onto the instrument, without damaging the wires or the
.
WIKA operating instructions pressure transmitter, model S-11