Determination of the Rotary Field
When connecting to a voltage >120V AC the glow
lamps are illuminated for phase control purpose.
"Press button ON (6). The green LED indicates that
the instrument is ready for testing.
"If the LED R (3) is illuminated, a clockwise rotary
field is present. If the LED L (4) is illuminated, a
counter-clockwise rotary field is present.
The phase control is displayed even if the neutral
conductor N is connected instead of L1, L2,or L3.
Imperatively verify correct phase connection car-
rying out a bipolar test using a voltage tester, e.g.
UNITEST 2000 alpha.
Phase indication
Phasenanzeige
Phase rotation
Drehfeldrichtung
rotat. right
DF richtig
DF falsch
rotat. left
L1 missing
L1 fehlt
L2 missing
L2 fehlt
L3 missing
L3 fehlt
Also refer to table (as indicated on the instrument
rear)
6.0 Contact-free rotary field determina-
tion
Remove connected test leads to avoid injuries
caused by entanglement into rotating parts.
The safety measures of accident prevention reg-
ulations regarding the work with rotating machines
must be fulfilled!
The UNITEST M-Indicator allows the contact-free ro-
tary direction determination of a running synchronous
or asynchronous three-phase motor.