Wiring
Open PLS 200 only when supply voltage is switched off.
Select correct voltage using manual voltage jumper before
switching on the power supply.
All field wiring must have insulation suitable for at least 250 Vac.
A disconnect switch shall be in close proximity to the equipment and within easy
reach of the operator.
Unused cable conduit fittings must be locked with a closing element or plug.
Commissioning must be done only with a closed device.
Observe all pertinent rules and regulations of the country of installation.
European Standards
When mounting the PLS 200 in hazardous areas, make sure the customer
supplied cable gland and/or plugs are certified ATEX 100a flameproof. The
temperature range must be at least -20 to 80°C (-4 to 176°F). The minimum ingress
protection requirement of IP6x according to European Standard EN 60529 must be
satisfied. Observe special conditions for safe use of the cable gland as described
by the gland's approval documentation.
The requirements of European Standard EN 50281-1-2 regarding dust deposits
and temperatures must be followed.

Voltage Selector

Select the voltage by placing the voltage jumper over the pins as illustrated below.
7
6
5
Page 8
lamp
1
2
protective earth
terminal
Pointek PLS 200 – INSTRUCTION MANUAL
voltage
jumper
24 V
115 V
230 V
7ML19981FS61