Specifications
Note:
Siemens Milltronics makes every attempt to ensure the accuracy of these
specifications but reserves the right to change them at any time. Please ensure these
are the most recent specifications.
Check our web site at www.siemens-milltronics.com or contact your representative
for the most up-to-date information.
Power
• jumper selectable
• 115 Vac, 50 to 60 Hz, 4VA
• 230 Vac, 50 Hz, 6VA
• 24 Vdc, 2.5W
All voltages ±15% (including ±10% according to IEC 61010-1)

Alarm Output

• microswitch SPDT contact 5A at 250 Vac, non-inductive
microswitch SPDT contact 4A at 30 Vdc, non-inductive
• alarm delay: approximately 1.3 seconds
Mechanical
Enclosure material
• epoxy coated aluminum
Process connection
• thread 1¼" NPT, 1½" BSP
• material: stainless steel 303 (1.4305)
Conduit entry
• 2 x M20 x 1.5
• 2 x ½" NPT
Page 2
Pointek PLS 200 – INSTRUCTION MANUAL
7ML19981FS61