en
Safety information
Installation, connection, commissioning
and repair work may only be carried out
by authorised technicians. This techni-
cian will be able to determine suitable
methods for securing the extractor hood
and providing the necessary exhaust air
ducting. The choice of attachment must
take account of the weight of the extrac-
tor hood and the load exerted on the
supporting surface. Note the extraction
values of the dowels supplied. Depend-
ing on the supporting surface, these
have the following values: Dowel Ø10
mm, concrete B25 9.4 kN brick Z20 5.2
KN solid calcium silicate KSV20 4.8 KN.
In the case of unstable supporting sur-
faces, a construction specialist such as
a structural engineer or architect must
be consulted to ensure the extractor
hood is safely installed.
Risk of injury!
The hood body may have sharp edges
resulting from the manufacturing pro-
cess. For this reason, safety gloves
must always be worn when installing it.
Risk of electric shock
The mains voltage must match the de-
tails indicated on the type plate. This
plate is located inside the hood near the
filter. Please only connect the extractor
hood to a properly installed safety sock-
et. This socket must be easily accessi-
ble after the installation so that the ex-
tractor hood can be disconnected from
the power supply if necessary. If a fixed
connection is used (e.g. if a suitable wall
socket is not available), the extractor
hood may only be connected by a quali-
fied electrician. For fixed connections,
the extractor hood must be connected to
a single power circuit fitted with an iso-
lating device. Isolating devices include
switches with a contact gap of at least 3
mm and all-pole switches, e.g., circuit
breakers and contactors. Before working
on the electrical connection of the ex-
12
tractor hood commences, the mains
circuit/circuits must always be switched
off. Before drilling the mounting holes,
please make sure that no electrical ca-
bles can be damaged during drilling.
The electrical connection must be pre-
pared in such a way as to allow the easy
connection of the extractor hood. Local
regulations must be observed.
Exhaust air ducting (for extrac-
tion mode)
Exhaust kitchen air must not be fed into
a chimney flue that is also used for the
exhaust air from devices using fuels
(e.g., gas). Official regulations regarding
ducting of exhaust air must be observed.
The exhaust air path must be prepared
in such as way as to allow the easy con-
nection of the extractor hood. The ex-
haust air hose must not have any kinks.
If the extractor hood is operated in ex-
traction mode at the same time as other
room-air-dependent
(e.g., wood, gas, oil or coal-fired appli-
ances) in the same room, lethal com-
bustion gases may be directed back into
the room due to the resulting negative
pressure. The operator must therefore
provide a sufficient air supply at all
times. The negative pressure in the
room must not exceed 4 Pa (0.04 mbar).
Solid fuel appliances
The installation of the extractor hood
above solid fuel appliances, which can
pose a fire hazard, (e.g., flying sparks) is
only permissible if the solid fuel appli-
ance is equipped with a sealed, non-
removable cover.
Minimum clearance to hob
The devices are designed for installation
flush with the ceiling. To prevent the
formation of condensation, a non-return
valve must be fitted directly outside the
air outlet. Please note the relevant appli-
cable installation regulations and instal-
lation instructions provided by the manu-
facturer of the gas appliance. The ex-
tractor hood may only be installed at
fire
appliances