Description
1762-
L24AWA,
L24AWAR
Shock
Operating: 30G; 3 pulses each direction, each axis
Relay Operation: 7G
Non-Operating: 50G panel mounted (40G DIN Rail mounted); 3 pulses each direction, each
axis
• UL 508
Agency
Certification
• C-UL under CSA C22.2 no. 142
• Class I, Div. 2, Groups A, B, C, D
• CE/C-Tick compliant for all applicable directives
Electrical/EMC
The controller has passed testing at the following levels:
• IEC1000-4-2: 4 kV contact, 8 kV air, 4 kV indirect
• IEC1000-4-3: 10V/m, 80 to 1000 MHz, 80% amplitude modulation, +900 MHz keyed
• IEC1000-4-4: 2 kV, 5 kHz; communications cable: 1 kV, 5 kHz
• IEC1000-4-5: communications cable 1 kV galvanic gun
• IEC1000-4-6: 10V, communications cable 3V
Terminal Screw
0.791 Nm (7 in-lb) rated
Torque
(1)
Do not allow the total load power consumed by the 5V dc, 24V dc, and sensor power outputs to exceed 12W.
(2)
Do not allow the total load power consumed by the 5V dc, 24V dc, and sensor power outputs to exceed 16W.
Refer to the MicroLogix 1200 User Manual for system validation worksheets.
L24BWA,
L24BWAR
(UL 1604, C-UL under CSA C22.2 no. 213)
carrier
I/O: 2 kV CM (common mode), 1 kV DM (differential mode)
AC Power Supply: 4 kV CM (common mode), 2 kV DM (differential mode)
DC Power Supply: 500V CM (common mode), 500V DM (differential mode)
MicroLogix™ 1200 Programmable Controllers
L24BXB,
40AWA,
L24BXBR
40AWAR
Publication 1762-IN006D-MU-P - March 2004