• Make sure the electrical imbalance ratio is no greater than 2%. If it is
larger than this, the unit's lifespan will be reduced.
If the ratio exceeds 4%, the unit will shut down and an malfunction
code will be displayed on the indoor remote controller.
• Connect the wire securely using designated wire and fix it with
attached clamp without applying external pressure on the terminal
parts (terminal for power wiring, terminal for transmission wiring
and ground terminal).
• If there exists the possibility of reverse-phase, lose phase, mo-
mentary blackout or the power goes on and off while the product is
operating, attach a reverse-phase protection circuit locally.
Running the product in reverse-phase may break the compressor
and other parts.
9 . 1 . Power circuit, safety device and cable requirements
• Make sure to apply the rated voltage of 575V for the unit.
Never connect 460V or 230V power supply.
• A power circuit (see the following table) must be provided for con-
nection of the unit. This circuit must be protected with the required
safety devices, i.e. a main switch, a slow blow fuse on each phase.
• When using residual current operated circuit breakers, be sure to
use a high-speed type (0.1 seconds or less) 200 mA rated residual
operating current.
• Use copper conductors only.
• Use insulated wire for the power cord.
• Select the power supply cable type and size in accordance with
relevant local and national regulations.
Phase and
Model name
Voltage
frequency
f3, 60Hz
REYQ72TAYCU
575V
REYQ96TAYCU
f3, 60Hz
575V
f3, 60Hz
REYQ120TAYCU
575V
REYQ144TAYCU
f3, 60Hz
575V
f3, 60Hz
REYQ168TAYCU
575V
f3, 60Hz
REYQ192TAYCU
575V
REYQ216TAYCU
f3, 60Hz
575V
f3, 60Hz
REYQ240TAYCU
575V
REYQ264TAYCU
f3, 60Hz
575V
f3, 60Hz
REYQ288TAYCU
575V
REYQ312TAYCU
f3, 60Hz
575V
f3, 60Hz
575V
REYQ336TAYCU
f3, 60Hz
REYQ360TAYCU
575V
REYQ384TAYCU
f3, 60Hz
575V
19
Maximum
Minimum
Transmission
overcurrent
circuit amp.
line selection
protective device
15.1
20
AWG18-16
16.8
20
AWG18-16
18.2
25
AWG18-16
22.3
30
AWG18-16
24.9
30
AWG18-16
16.8+16.8
20+20
AWG18-16
16.8+18.2
20+25
AWG18-16
18.2+18.2
25+25
AWG18-16
18.2+22.3
25+30
AWG18-16
22.3+22.3
30+30
AWG18-16
22.3+24.9
30+30
AWG18-16
24.9+24.9
AWG18-16
30+30
18.2+18.2+18.2
25+25+25
AWG18-16
18.2+18.2+22.3
25+25+30
AWG18-16
9 .2 . Wiring connection example for whole system
1 1
2
2
4
3
1
Power supply
2
Main switch
3
Fuse or circuit breaker
4
Outdoor unit
5
COOL/HEAT selector
6
Remote controller
7
Indoor unit
8
Branch Selector unit
This image is intended as an example only. Please follow local and
national electrical code.
NOTE
• Make sure the low voltage wiring (i.e. for the remote controller, between
units) and the power wiring do not pass near each other, keeping them at
least 2 in. (51 mm) apart.
Proximity may cause electrical interference, malfunctions, and breakage.
• Be sure to connect the power wiring to the power wiring terminal block
and secure it as described in 9.5. Power wiring connection procedure.
• Transmission wiring should be secured as described in 9.4. Trans-
mission wiring connection procedure.
• Secure wiring with clamp such as insulation lock ties to avoid con-
tact with piping.
• Shape the wires to prevent the structure such as the control box
cover deforming. And close the cover firmly.
• All field wiring is to be procured on site.
9 .3 . leading wire procedure
• The power wiring and ground wiring are passed out from the power
wiring hole on the front (knock hole).
• The transmission wiring is passed out from the wiring hole (knock
hole) on the front of the unit.
REYQ72-168T type
1
Wiring diagram printed on the back of the control box cover.
2
Knockout hole
3
Power line
4
Transmission line
8