1.1 GENERAL CHARACTERISTICS
Digital microprocessor power factor controller.
−
3-phase voltage measurement input, separate from the power supply.
−
2 serial interfaces (1 RS232 and 1 RS485 ports) for set-up, remote control, supervi-
−
sion and automatic testing via PC.
Internal temperature sensor.
−
Programmable input for external temperature sensor (NTC) or for digital input.
−
Clock/calendar with event log.
−
Advanced functions (measurement of capacitor overload current, FFT (harmonic spec-
−
trum) on current and voltage up to 31st harmonic, average weekly power factor, sav-
ing of maximum values, saving of harmonic events).
2 relays programmable as alarm and/or fan control.
−
1.2 FRONT PANEL
3 digit 7-segment
LED display
LED indicating type
of load detected
LED indicating
multiplier
LED indication of
measurement on
the display
1.3 INSTALLATION
Install the controller according to the wiring diagrams provided at page n°52, taking care
to connect the CT on the correct phase.
The controller automatically recognizes the CT current flow. In case of co-generation sys-
tems, disable this function (refer to "Advanced menu set-up" section) and connect the CT
correctly.
1. CONTROLLER MANUAL
4 digit 7-segment
LED display
32
LED indication
of steps enabled
LED indication
LED indication
of operation
5 membrane key keypad access
the controller functions
of alarms
(if preset)
selected