1.20 ADVANCED MENU TABLE OF PARAMETERS
PARAM.
P.11
CT connection recognition
P.12
Capacitors rated frequency selection
P.13
RPA - Step power adjustment
P.14
RPE - Step power adjustment
P.15
P.16
Co-generation cosφ set-point
P.17
RPA - Disconnection sensitivity
P.18
RPE - Disconnection sensitivity
P.19
at change to MANU mode
Capacitor overload alarm threshold
P.20
Overload threshold for immediate step
P.21
Overload event counter reset time
P.22
Overload alarm reset time
P.23
Unit of measure for temperature
P.24
P.25
P.26
Temperature alarm threshold
P.27
Refer to the wiring diagrams and the programming notes.
FUNCTION
Type of connection
Adjustment mode
Step connection mode
Step disconnection
disconnection
Fan start temperature
Fan stop temperature
RANGE
A.COn 3-phase
B.COn 1-phase
C.COn Full 3-phase
d.COn 3-phase L1-N
E.COn MV 3-phase
Aut Automatic
dir Direct
rEU Inverse
Aut Automatic
50H 50Hz
60H 60Hz
On Enabled
OFF Disabled
OFF Disabled
Std Standard
Bnd Band
Std Standard
Lin Linear
0.80 Ind ... 0.80 Cap
1 ... 600sec
OFF Disabled
On Enabled
100 ... 150 %
100 ... 200 %
1 ... 240h
1 ... 30min
°C °Celsius
°F °Fahrenheit
0 ... 100 °C
32 ... 212 °F
0 ... 100 °C
32 ... 212 °F
50 ... 100 °C
122 ... 212 °F
41
DEFAULT
A.COn
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Aut
Aut
Std
Std
125
150
24
5
°C
55
50
60